Flame Detector Replacements

Upgrade paths for discontinued flame sensors from Honeywell and Siemens, ensuring safety and compliance.

Configuration Mismatch Risk

Although replacements like C7027A/C7061A may fit physically ("Direct Mechanical Interchange"), they often require specific amplifiers (e.g., R7849 vs R7861) based on Intermittent vs. Continuous operation. Mismatched components can lead to false alarms or failure to detect flame loss.

Replacement List

BrandDiscontinued ModelEnd of LifeOfficial ReplacementKey DifferencesInterchange?Action / Advice
HoneywellC7927 (Solid State UV)2022-12-30C7027A (Powertube UV)Mechanical: Same housing (no mech mod). Electrical: Needs R7849 (Intermittent) for 7800 Series or R8001S1071 for SLATE.ConditionalMust lock in Amplifier Model + Operation Mode (Intermittent/Continuous) to avoid false alarms.
HoneywellC7961E/F (Self-Check UV)2022-12-30C7061A/F (Powertube UV, Self-Check)Mechanical: Same housing. Electrical: Needs R7861 (Continuous) for 7800 Series or R8001S1051 for SLATE. Check ATEX/UL.ConditionalFor hazardous areas, strictly verify ATEX/UL zones and specific sub-models.
HoneywellIFW-15 (Intermittent)2022-12-30Honeywell Kromschröder FDU SeriesFDU is new generation. Requires wiring/parameter matching. OEM approval suggested.ConditionalSelect FDU 510/520 based on operation mode (intermittent/continuous) and sensor type (Ion/UV).
HoneywellIFW-50 (Continuous)2022-12-30Honeywell Kromschröder FDU SeriesSame as above. For continuous operation.ConditionalPrioritize FDU 520 (Continuous) and perform threshold/response time tests.
HoneywellR4343 (Flame Switch)2022-12-30Honeywell Kromschröder FDU SeriesCompliance Risk: R4343 does NOT meet new EU requirements (GAR/LVD/EMCD). Replacement only.ConditionalDo NOT use R4343 for new EU/UK installations. Migrate existing units to FDU.
HoneywellC7076F (Hazardous UV)Discontinued SoonU2-101xS-PF SeriesFunctional replacement (UV/IR). Requires system-level signal/setting adjustment.ConditionalHazardous areas must verify Sensor + Amplifier/Controller certification package.
SiemensQRB1A-A050B70ADiscontinuedLikely QRB4 (Verify)No official map. QRB4 is common for oil yellow flame. Verify suffix (length/plug).ConditionalCheck exact suffix. Obtain OEM confirmation.
SiemensQRB3(1)DiscontinuedLikely QRB4 (Verify)No official map. Engineering review required.ConditionalPerform functional tests (extraneous light, response time) and document results.

Priority Procurement & Maintenance Advice

  • Honeywell C7927/C7961: Lock in the "Controller Platform + Amplifier Model + Operation Mode" as a single BOM item.
  • Regulatory Compliance: R4343 and older relays may not meet current EU standards. New installations in regulated regions should migrate directly to the FDU Series.
  • Siemens QRB Series: Do not rely solely on visual similarity. Verify the exact suffix and obtain OEM approval before use.