Skip to content
Industrial combustion components support@rifuze.com

Azbil

Azbil R4780C220 flame safeguard controller

Azbil R4780C220 · view 1
Model
R4780C220

Get a quote

Azbil · R4780C220

Programmable flame safeguard controller (Protectorelay) that provides automatic ignition control and combustion safety monitoring for batch-operated oil-fired, gas-fired, or oil/gas-fired burners with a combustion capacity of 350 kW or more.

Technical Specifications

Massapprox. 1.0 kg
ModelR4780C220
Mountingplug-in to subbase Q241A100
Case colorLight gray
AccessoriesQ241A100 subbase and surge absorber 83968019-001 (for R4780C/D/F) supplied as standard; optional flame simulator 123514B, FSP300C flame simulator, analog flame meter FSP136A100
ApplicationsUsed in gas trains and control panels of industrial boilers, heat-treatment furnaces, and process combustion equipment that operate in batch mode, where automatic ignition sequencing and flame failure lockout protect the installation.
Key featuresC-series variant compatible with an ultraviolet flame detector (C7012A per the official user's manual); this listing is a 220 V AC version commonly supplied for the Chinese market.; Status indicator LEDs show sequence progress: pre-purge/post-purge, ignition trial, pilot-only, main trial, run, and flame/alarm.; Built-in ground fault detection circuit shuts down and locks out combustion equipment if a ground fault occurs in the valve, ignition transformer, or similar loads.; Safe start circuit prevents startup on external circuit failure or false flame signal; a pilot-only proving period ensures safe operation even if the detector sees an ignition spark.; On lockout, the burner cannot restart without manual reset via the reset button.; Supports both three-position and proportional combustion control; plug-in mounting on subbase model Q241A100.; Power consumption 9 W +25% max.; ambient temperature -20 to +60 °C, 90 % RH at 40 °C; mass approx. 1.0 kg.; Sequence timing per selection guide: pre-purge 35 ± 5 s, ignition trial 7.5 ± 2.5 s, pilot stabilization 8.5 ± 3.5 s, main trial 6.5 ± 2 s, post-purge 8.5 ± 3 s.
Lockout time30 s or less
Flame current2 to 6 uA at the test jack (R4780B); 4 uA or more at the test jack (R4780C); detection sensitivity 2 uA or less and flame-out sensitivity 0.8 uA or more (R4780C)
Prepurge time35 +/-5 s
Flame response1.5 +/-0.5 s at a flame current of 8.5 uA (R4780C)
Postpurge time20 +/-8 s
Product statusDiscontinued
Main trial time6.5 +/-2 s
Pilot only time8.5 +/-3.5 s
Ambient humidity90 %RH or less at 40 deg C
Product categoryIndustrial combustion component - flame safeguard controller (Protectorelay burner controller)
Shock resistance300 m/s2 or less (durability)
Allowable voltage85 to 110 % of rated voltage
Operating voltage220 V AC 50/60 Hz (per distributor data)
Power consumption9 W +25% max.
Ignition wait time7.5 +/-2.5 s
Rated power supply220 V AC, 50/60 Hz
Ambient temperature-20 to +60 °C
Dielectric strength1500 V AC for 1 min or 1800 V AC for 1 s between each terminal (except 23 and 24) and ground; remove the surge absorber wiring before testing
Ignition trial time4 +/-1 s
Storage temperature-25 to +70 deg C
Contact rating alarm75 VA (terminal 21)
Main stabilized time8.5 +/-3.5 s
Vibration resistance4.9 m/s2 or less, 10 to 55 Hz, 2 h each in X, Y, Z directions
Contact rating blower120 V AC, 4 A / 240 V AC, 2 A (terminal 3)
Insulation resistance50 Mohm or more with a 500 V DC megger between each terminal (except 23 and 24) and ground
Total load normal run6 A max.
Flame signal wire lengthC7027A/C7035A: approx. 200 m with 2 mm2 IV cable; C7007A/C7008A: approx. 30 m with RG-11/U; C7012A: approx. 50 m
Contact rating main valve800 VA (terminal 7)
Lightning surge protection10 kV, 1.2/50 us (JEC-212, surge impedance 75 ohm min.) with the surge absorber between ground and one side of the power supply (terminal 2)
Contact rating control motor200 VA (terminals 8, 9, 10, 11)
Applicable combustion capacity350 kW or more for batch operation (current manuals); the earlier English selection guide states 580 kW / 500,000 kcal/h or greater
Ground fault detection resistance10 kohm or more (at normal temperature and humidity, rated voltage)
Contact rating ignition transformer400 VA (terminal 4)
Contact rating interrupted pilot valve400 VA (terminal 6)
Contact rating intermittent pilot valve400 VA (terminal 5)

Burner control: purchasing checks

Review these fields for the complete ordering code. Unconfirmed fields can be included with your enquiry.

Operating voltage
220 V AC 50/60 Hz (per distributor data)
Operating sequence
To be confirmed for the exact model
Flame supervision
To be confirmed for the exact model
Operating mode
To be confirmed for the exact model
Wiring / base
To be confirmed for the exact model
Program / configuration
To be confirmed for the exact model

Supply information

The quotation confirms the actual items, accessories and commercial terms for your order.

Item condition
To be confirmed in your quotation
Packaging
To be confirmed in your quotation