Azbil R4780C1019 Protectorelay FSG80 flame safeguard control

Azbil R4780C1019 · view 1
Model
R4780C1019

Get a quote

Azbil · R4780C1019

Provides automatic sequence control, flame supervision and safety lockout for batch operation of oil-fired, gas-fired or oil/gas-fired burners with a combustion capacity of 350 kW or more, shutting off fuel and raising an alarm when a flame failure occurs.

Technical Specifications

MassApproximately 1.0 kg
ModelR4780C1019
MountingPlugs into subbase Q241A100 attached with screws; mounting direction unrestricted except that the reset button cannot face downward
Case colorLight gray
AccessoriesQ241A100 subbase and surge absorber 83968019-001 (for R4780C/D/F) supplied as standard; optional flame simulator 123514B, FSP300C flame simulator and analog flame meter FSP136A100
ApplicationsUsed in flame safeguard systems of batch-operated oil, gas or combination burners rated 350 kW and above, such as industrial boilers, furnaces and process heating equipment, for automatic start sequence, flame monitoring, alarm and lockout.
Key featuresModel R4780C1019 (R4780C1019-2 in the official manual) is the 200 V AC version of the R4780C, which uses compact ultraviolet sensors C7027A or C7035A.; Sequence timing: prepurge 35 ± 5 s, ignition wait 7.5 ± 2.5 s, ignition trial 4 ± 1 s, pilot-only 8.5 ± 3.5 s, main trial 6.5 ± 2 s, postpurge 20 ± 8 s and lockout 30 s or less; flame response 1.5 ± 0.5 s at an 8.5 µA flame current.; Built-in ground fault detection circuit; a pilot-only proving period ensures safety even if the detector sees the ignition spark.; Flame current of 4 µA or more at the test jack; flame detection sensitivity 2 µA or less; a status indicator displays the progress of the control sequence.; Power consumption 11.25 W max.; ambient temperature -20 to +60 °C; weight approximately 1.0 kg; plugs into a screw-mounted subbase.; Allowable voltage 85 to 110 % of rated voltage; insulation resistance 50 MΩ min.; dielectric strength 1500 V AC for 1 minute.
Lockout time30 s or less
Flame current4 µA or more at the test jack (R4780C); detection sensitivity 2 µA or less and flame-out sensitivity 0.8 µA or more
Prepurge time35 ± 5 s
Flame detectorC7027A or C7035A compact ultraviolet sensor
Flame response1.5 ± 0.5 s (at 8.5 µA flame current)
Postpurge time20 ± 8 s
Product statusDiscontinued
Main trial time6.5 ± 2 s
Pilot only time8.5 ± 3.5 s
Prepurge timing35 ± 5 s
Ambient humidity90 %RH or less at 40 °C
Product categoryIndustrial combustion safety - Protectorelay FSG80 flame safeguard control (programmable burner safety controller)
Shock resistance300 m/s² or less (durability)
Allowable voltage85 to 110 % of rated voltage
Operating voltage200 V AC, 50/60 Hz
Power consumption11.25 W max.
Ignition wait time7.5 ± 2.5 s
Rated power supply200 V AC, 50/60 Hz (official manual model table: R4780C1019-2)
Ambient temperature-20 to +60 °C
Dielectric strength1500 V AC for 1 min or 1800 V AC for 1 s between each terminal (except 23 and 24) and ground; remove the surge absorber wiring before testing
Ignition trial time4 ± 1 s
Min burner capacity350 kW
Storage temperature-25 to +70 °C
Contact rating alarm75 VA (terminal 21)
Main stabilized time8.5 ± 3.5 s
Vibration resistance4.9 m/s² or less, 10 to 55 Hz, 2 h each in X, Y and Z directions
Contact rating blower120 V AC, 4 A / 240 V AC, 2 A (terminal 3)
Insulation resistance50 MΩ or more with a 500 V DC megger between each terminal (except 23 and 24) and ground
Total load normal run6 A max.
Compliance requirementThe burner body must be earth-grounded to the Japanese technical standard for Class D (formerly Class 3) grounding, with a ground resistance below 100 Ω
Flame signal wire lengthC7027A / C7035A: approx. 200 m with 2 mm² IV cable; C7007A/C7008A: approx. 30 m with RG-11/U; C7012A: approx. 50 m
Contact rating main valve800 VA (terminal 7)
Lightning surge protection10 kV, 1.2/50 µs (JEC-212, surge impedance 75 Ω min.) with the surge absorber between ground and one side of the power supply (terminal 2)
Contact rating control motor200 VA (terminals 8, 9, 10, 11)
Applicable combustion capacity350 kW or more for batch operation (current manuals); the earlier English selection guide states 580 kW / 500,000 kcal/h or greater
Ground fault detection resistance10 kΩ or more (at normal temperature and humidity, rated voltage)
Contact rating ignition transformer400 VA (terminal 4)
Contact rating interrupted pilot valve400 VA (terminal 6)
Contact rating intermittent pilot valve400 VA (terminal 5)

Supply information

The quotation confirms the actual items, accessories and commercial terms for your order.

Item condition
To be confirmed in your quotation
Packaging
To be confirmed in your quotation
Included accessories
To be confirmed in your quotation
Stock confirmation
To be confirmed in your quotation
Dispatch / lead time
To be confirmed in your quotation
Price conditions
To be confirmed in your quotation
Warranty provider
To be confirmed in your quotation

More components in this catalog