MassApprox. 3 kg
ModelECM3000G9100
MaterialCase: die-cast aluminium. Cover: polycarbonate resin with GF. Bracket: steel.
ProtectionIP54 or equivalent
ApplicationsApplied to burner control, hot or cold water and steam valve control and general industrial process positioning, where the 90-degree stroke type suits burner air damper applications and the 160-degree type suits valve control, replacing older Azbil control motors.
Input signal4 to 20 mA DC
Key featuresDecoded from the official type summary as the ECM3000G91 base: 85 to 264 V AC wide-range power supply, 4 to 20 mA DC input signal, 90-degree angular stroke, with no optional auxiliary switches and not GB-compliant.; Output torque 12.5 N·m; motor timing approximately 39 s for 90 degrees of travel at no load; power consumption 14 W during operation.; Position-proportional operation with zero point, span and dead band adjustable; direct/reverse operation switchable, factory set to direct action.; Splash-proof structure IP54 or equivalent; die-cast aluminum case with polycarbonate resin cover and steel bracket; weight approximately 3 kg.; Feedback potentiometer with nominal value 135 Ω (combined resistance) and maximum applied voltage 5 V DC; repeatability less than ±3 %.; Ambient operating conditions -20 to +60 °C and 5 to 95 %RH without condensation; vibration resistance 4.9 m/s².; Standard bracket accessory allows retrofitting of older Azbil motors; compatible with Azbil controllers such as the SDC35/36, SDC45/46 and SDC40 series and DMC10.
Motor timingapprox. 39 s (no load)
Output torque12.5 N·m
RepeatabilityLess than ±3 %
Angular stroke90°
Operation modePosition proportional (direct/reverse operation switchable, zero point / span / deadband adjustable; factory-set to direct operation)
Operation typeTerminals 1-2: NO; terminals 1-3: NC
Optional partsCrank arm N-3128; damper arm J-26026G-ARM; valve linkage Q455C/D; damper linkage Q605A/D/E; base kit 83165292-001 for the V51E butterfly valve; waterproof connector 83104346-003; 24 V AC power supply transformer AT72-J1; extension units 83174065-002 / -102 (4 switches, 100 mA to 5 A) and 83174065-003 / -103 (4 switches, 1 to 100 mA); auxiliary potentiometer 83165272-001 (90° type) / -002 (160° type)
Product statusDiscontinued
Input impedanceEquivalent of 125 Ω or less at 20 mA (receiving resistance 45 Ω plus the resistance of the overcurrent protection circuit)
Ambient humidity5 to 95 %RH (no condensation allowed)
Product categoryIndustrial automation component - Electric control motor (rotary actuator for burner and valve control)
Storage humidity5 to 95 %RH (no condensation allowed)
Operating voltage85 to 264 V AC, 50/60 Hz
Power consumption14 W
Auxiliary switchesNone - the 11th digit is 0, i.e. "without options". An extension unit carrying four auxiliary switches (83174065-002 / -102 for 100 mA to 5 A, 83174065-003 / -103 for 1 to 100 mA) can be mounted on such a model; note *3 of the selection guide confirms this and adds that only one type of extension unit can be fitted.
Standard accessoryMounting bracket for replacing Azbil's older control motors - included as a standard accessory part
Ambient temperature-20 to +60 °C
Dielectric strength1500 V AC for 60 s between the power supply terminals and casing and between the input terminals and casing (85-264 V AC type); 1500 V AC for 60 s between the auxiliary switch terminals and casing
Replacement targetsAzbil's older control motors M904, M744 and M7284 can be replaced directly; terminals S, CONT, CW and CCW must then be wired with non-voltage contacts - never apply 24 V AC to them or the circuits may burn out
Storage temperature-20 to +70 °C
Vibration resistance4.9 m/s² in operation; 19.6 m/s² in transport/storage (packaged condition)
Insulation resistance5 MΩ or more by 500 V DC megger between the power supply terminals and casing and between the input terminals and casing; 20 MΩ or more between the auxiliary switch terminals and casing
Feedback potentiometerNominal 135 Ω (combined resistance 1 kΩ + 180 Ω), 0.5 W
Settable opening range5 to 95 % (must remain inside the end-switch range)
Auxiliary switch ratingNot applicable to this variant because no auxiliary switch is built in (11th digit 0). If an extension unit is fitted: standard type 250 V AC, 100 mA to 5 A resistive load and 100 mA to 3 A inductive load; low-current type 250 V AC, 1 to 100 mA inductive load including inrush current; if UL or CE compliance is required the rating is 30 Vrms or 42.4 V AC.
Factory switch positionsFor 90° angular stroke motors with built-in auxiliary switch, at factory settings: Close to Open (A, C) 9° ±5°; Open to Close (B, D) 81° ±5°
Potentiometer max voltage5 V DC
Auxiliary switch service lifeNot applicable to this variant (no built-in switch). Extension-unit switches follow the standard type (50,000 cycles or more) or the low-current type (200,000 cycles or more) figures.