ModelC6097A0310
OutputSPDT contact output
StandardsEN 1854 (GAR), certificate No. 0063AR1571/1; EN 60730-2-6 (LVD); JIS C 9730-2-6
Durability100,000 cycles or more at rated contact voltage and current
Net weight260 g
ApplicationsTypical applications include detecting upper and lower pressure limits of gas or air supplied to gas combustion equipment, burner blower interlock, and clogged filter detection in industrial burners and boilers.
Key featuresC6097A0310 setting range 3 to 15 kPa with a fixed nominal differential gap of 280 Pa; ON/OFF control operation.; Maximum allowable pressure 50 kPa; setting accuracy 3 ± 0.9 kPa and 15 ± 2.25 kPa at the range ends.; Applicable fluids: city gas, natural gas, LP gas, and air; usable as a negative or differential pressure switch for non-flammable gases.; SPDT contact output; contact rating 250 V AC 5 A resistive, 250 V AC 3 A inductive (power factor 0.6), minimum 50 mA at 24 V DC.; Setting dial calibrated in kPa; pressure meter port provided for monitoring; JIS-standard electrical conduit connectable.; Die-cast aluminum housing with NBR/nitrile rubber diaphragm; mass 260 g.; Allowable ambient and fluid temperature -15 to +60 °C; durability 100,000 cycles or more at rated contact conditions.; Conforms to CE standards: EN 1854 (GAR, certificate No. 0063AR1571/1) and EN 60730-2-6 (LVD); JIS C 9730-2-6.
Setting range3 to 15 kPa
Auxiliary partSwitch-operated indicator lamp 100/200 V AC, model 81404156 (sold separately)
Contact rating250 V AC, 5 A resistive / 3 A inductive
Pressure portsRp 1/4 high-pressure port with plug (6 mm hex wrench); Rp 1/8 low-pressure port with dust seal
Wiring terminalM3.5 screw terminal; wiring port 22 mm diameter
Differential gap280 Pa (fixed)
Product categoryIndustrial combustion component - gas pressure switch for burner gas trains
Setting accuracy3 +/-0.9 kPa and 15 +/-2.25 kPa at the range ends (low pressure side at atmospheric pressure; high pressure side when the pressure rises)
Applicable fluidsCity gas, natural gas, LP gas, air
Contact operationPressure rising: terminals 1-3 open, 2-3 closed. Pressure falling: terminals 1-3 closed, 2-3 open
Control operationON/OFF
Withstand voltage600 V AC 50/60 Hz for 1 min between terminals of the same polarity; 1500 V AC 50/60 Hz for 1 min between each terminal and the non-charged metal part; leakage current 1 mA or less
Contact resistance100 mohm or less initially (voltage drop method at 6 to 8 V DC and 1 A)
Enclosure materialPBT (polybutylene terephthalate) case with a transparent polycarbonate cover
Product dimensionsWidth 69 mm; height 86 mm; depth 69 mm
Installation positionVertical, or horizontal with the pressure-setting dial facing upward
Insulation resistance100 Mohm or more between each terminal and the non-charged metal part, with a 500 V DC megger
Operating temperature-15 to +60 °C
Max allowable pressure50 kPa
Maximum allowable pressure50 kPa
Allowable fluid temperature-15 to +60 deg C (without freezing or condensation)
Allowable ambient temperature-15 to +60 deg C (without freezing or condensation)
Electric shock protection classClass I
Gas contacting material high pressure sideDie-cast aluminium (housing), NBR/nitrile rubber (diaphragm)