Azbil AUR890G630S01 Burner controller

Azbil AUR890G630S01 · view 1
Model
AUR890G630S01

Get a quote

Azbil · AUR890G630S01

Operates combustion equipment according to a predefined sequence and timing, supervising the burner flame and locking out the system on ignition failure or flame failure; developed as a direct upgrade replacement for the Protectorelay model RA890.

Technical Specifications

MassApprox. 600 g including the subbase; approx. 1200 g with the Q890A100 replacement base unit
InputNon-voltage contact input, allowable contact resistance 500 Ω max. (start, lockout interlock, contact reset, airflow switch and similar)
ModelAUR890G630S01
MountingDIN rail mounting or direct mounting through base screw holes; vertical or horizontal, but in horizontal mounting the 7-segment display must face directly upward; mounting angle reference plane ±10°
ProtectionIP40 (with sideboards)
ApplicationBatch-operated combustion systems burning gas, oil or a gas/oil mixture
ApplicationsApplied to batch-operated gas, oil or gas/oil combination burners in industrial boilers, heating furnaces and process heating equipment for ignition sequence control, flame monitoring and automatic safety lockout.
Key featuresModel AUR890G630S01 is the 220 V AC version with ultraviolet flame detection using the AUD100/110/120 series advanced UV flame detectors; flame response time 3 ± 1 s at a 3 V DC flame voltage.; Designed for batch operation with at least one start and stop per 24-hour period; has no built-in pre-purge function, so system design must consider pre-purge timing.; Power consumption 10 W or less; contact ratings: ignition transformer 300 VA, pilot valve 200 VA, main valve 200 VA and alarm 75 VA.; Flame voltage is shown on a 7-segment display; the recommended stable flame voltage is 2 V DC or above.; Sequence and alarm codes are displayed on lockout for troubleshooting; flame and alarm indicator LEDs show operating status.; Protection rating IP40 with sideboards (IP10 with the sub-base only); case of denatured PPE resin; approximately 600 g including the sub-base.; Can replace the RA890 using base unit Q890A100 with the same mounting holes and terminals; sub-base BC-R05A100 and sideboards are sold separately.
Reset timing1 s or longer (reset switch or contact reset input); a reset input is not accepted when no alarm has occurred
Service life10 years at 8 hours per day, or 100,000 start/stop cycles (at 25 °C, room temperature and humidity, rated voltage)
Case materialDenatured PPE resin (UL94-V0, PTI material group IIIa), black
Contact ratingIgnition transformer 300 VA / pilot valve 200 VA / main valve 200 VA / alarm 75 VA
Flame detectorAUD100/110/120 series advanced UV flame detector
Flame response3 ± 1 s (at 3 V DC flame voltage)
Lockout timing13.5 ± 1.5 s
Optional partsDedicated subbase BC-R05A100, sideboards 81447515-001, base unit Q890A100 for RA890 replacement, front wiring connectors 81447514-001 / -002, loader jack cover 81447519-001, front connector cover 81447531-001, analog flame meter FSP136A100
Purge functionNone built in - an external purge circuit is required; Azbil recommends pairing the controller with its igniter S7200A
Pollution degreePD2
Product categoryIndustrial combustion safety - Burner controller (combustion safety device for batch-operated burners)
Shock resistance0 to 9.8 m/s² during operation; 0 to 300 m/s² during transport/storage
Storage humidity5 to 95 %RH (no condensation)
Operating voltage220 V AC, 50/60 Hz
Power consumption10 W or less
Protection ratingIP40 with sideboards 81447515-001 fitted to the subbase BC-R05A100; IP10 with only the Q890A100 base unit or the bare subbase
Rated power supply220 V AC, 50/60 Hz
Dielectric strength1500 V AC for 1 min or 1800 V AC for 1 s between each terminal (except flame detector terminals 14 and 15) and ground (the DIN rail clamp)
Flame establishment1.5 to 4.5 V DC (AUD100/110/120 UV sensor)
Flame out detection0.2 to 0.6 V DC (AUD100/110/120 UV sensor)
Storage temperature-20 to +70 °C
Contact rating alarm75 VA
Overvoltage categoryII
Standards complianceJIS C 9730-2-5:2010
Vibration resistance0 to 3.2 m/s² during operation; 0 to 9.8 m/s² during transport/storage (10 to 150 Hz)
Insulation resistance50 MΩ min. with a 500 V DC megger between each terminal (except terminals 14 and 15) and ground
Flame failure response3 ± 1 s at a flame voltage of 3 V DC (UV sensor; selected by the flame-response digit 3)
Contact rating main valve200 VA
Recommended flame voltageStable 2 V DC or above
Contact rating pilot valve200 VA
False flame detection time15 s
Flame voltage output range0.2 to 4.5 V DC (UV sensor)
Operating ambient humidity10 to 90 %RH (no condensation)
Operation at flame failureLockout
Operating ambient temperature-20 to +60 °C
Operation at ignition failureLockout
Allowable power supply voltage85 to 110 % of rated power supply
Main burner combustion standby0.4 s
Contact rating ignition transformer300 VA (100 / 200 / 220 V AC models); 360 VA on the AC120 V model AUR890G330
Ignition wait time from start check3 ± 0.3 s

Burner control: purchasing checks

Review these fields for the complete ordering code. Unconfirmed fields can be included with your enquiry.

Operating voltage
220 V AC, 50/60 Hz
Operating sequence
To be confirmed for the exact model
Flame supervision
To be confirmed for the exact model
Operating mode
To be confirmed for the exact model
Wiring / base
To be confirmed for the exact model
Program / configuration
To be confirmed for the exact model

Supply information

The quotation confirms the actual items, accessories and commercial terms for your order.

Item condition
To be confirmed in your quotation
Packaging
To be confirmed in your quotation
Included accessories
To be confirmed in your quotation
Stock confirmation
To be confirmed in your quotation
Dispatch / lead time
To be confirmed in your quotation
Price conditions
To be confirmed in your quotation
Warranty provider
To be confirmed in your quotation

More components in this catalog