MassApprox. 600 g including the subbase; approx. 1200 g with the Q890A100 replacement base unit
InputNon-voltage contact input, allowable contact resistance 500 Ω max. (start, lockout interlock, contact reset, airflow switch and similar)
ModelAUR890G630S01
MountingDIN rail mounting or direct mounting through base screw holes; vertical or horizontal, but in horizontal mounting the 7-segment display must face directly upward; mounting angle reference plane ±10°
ProtectionIP40 (with sideboards)
ApplicationBatch-operated combustion systems burning gas, oil or a gas/oil mixture
ApplicationsApplied to batch-operated gas, oil or gas/oil combination burners in industrial boilers, heating furnaces and process heating equipment for ignition sequence control, flame monitoring and automatic safety lockout.
Key featuresModel AUR890G630S01 is the 220 V AC version with ultraviolet flame detection using the AUD100/110/120 series advanced UV flame detectors; flame response time 3 ± 1 s at a 3 V DC flame voltage.; Designed for batch operation with at least one start and stop per 24-hour period; has no built-in pre-purge function, so system design must consider pre-purge timing.; Power consumption 10 W or less; contact ratings: ignition transformer 300 VA, pilot valve 200 VA, main valve 200 VA and alarm 75 VA.; Flame voltage is shown on a 7-segment display; the recommended stable flame voltage is 2 V DC or above.; Sequence and alarm codes are displayed on lockout for troubleshooting; flame and alarm indicator LEDs show operating status.; Protection rating IP40 with sideboards (IP10 with the sub-base only); case of denatured PPE resin; approximately 600 g including the sub-base.; Can replace the RA890 using base unit Q890A100 with the same mounting holes and terminals; sub-base BC-R05A100 and sideboards are sold separately.
Reset timing1 s or longer (reset switch or contact reset input); a reset input is not accepted when no alarm has occurred
Service life10 years at 8 hours per day, or 100,000 start/stop cycles (at 25 °C, room temperature and humidity, rated voltage)
Case materialDenatured PPE resin (UL94-V0, PTI material group IIIa), black
Contact ratingIgnition transformer 300 VA / pilot valve 200 VA / main valve 200 VA / alarm 75 VA
Flame detectorAUD100/110/120 series advanced UV flame detector
Flame response3 ± 1 s (at 3 V DC flame voltage)
Lockout timing13.5 ± 1.5 s
Optional partsDedicated subbase BC-R05A100, sideboards 81447515-001, base unit Q890A100 for RA890 replacement, front wiring connectors 81447514-001 / -002, loader jack cover 81447519-001, front connector cover 81447531-001, analog flame meter FSP136A100
Purge functionNone built in - an external purge circuit is required; Azbil recommends pairing the controller with its igniter S7200A
Pollution degreePD2
Product categoryIndustrial combustion safety - Burner controller (combustion safety device for batch-operated burners)
Shock resistance0 to 9.8 m/s² during operation; 0 to 300 m/s² during transport/storage
Storage humidity5 to 95 %RH (no condensation)
Operating voltage220 V AC, 50/60 Hz
Power consumption10 W or less
Protection ratingIP40 with sideboards 81447515-001 fitted to the subbase BC-R05A100; IP10 with only the Q890A100 base unit or the bare subbase
Rated power supply220 V AC, 50/60 Hz
Dielectric strength1500 V AC for 1 min or 1800 V AC for 1 s between each terminal (except flame detector terminals 14 and 15) and ground (the DIN rail clamp)
Flame establishment1.5 to 4.5 V DC (AUD100/110/120 UV sensor)
Flame out detection0.2 to 0.6 V DC (AUD100/110/120 UV sensor)
Storage temperature-20 to +70 °C
Contact rating alarm75 VA
Overvoltage categoryII
Standards complianceJIS C 9730-2-5:2010
Vibration resistance0 to 3.2 m/s² during operation; 0 to 9.8 m/s² during transport/storage (10 to 150 Hz)
Insulation resistance50 MΩ min. with a 500 V DC megger between each terminal (except terminals 14 and 15) and ground
Flame failure response3 ± 1 s at a flame voltage of 3 V DC (UV sensor; selected by the flame-response digit 3)
Contact rating main valve200 VA
Recommended flame voltageStable 2 V DC or above
Contact rating pilot valve200 VA
False flame detection time15 s
Flame voltage output range0.2 to 4.5 V DC (UV sensor)
Operating ambient humidity10 to 90 %RH (no condensation)
Operation at flame failureLockout
Operating ambient temperature-20 to +60 °C
Operation at ignition failureLockout
Allowable power supply voltage85 to 110 % of rated power supply
Main burner combustion standby0.4 s
Contact rating ignition transformer300 VA (100 / 200 / 220 V AC models); 360 VA on the AC120 V model AUR890G330
Ignition wait time from start check3 ± 0.3 s