Azbil AUR890G630 burner controller

Azbil AUR890G630 · view 1
Model
AUR890G630

Get a quote

Azbil · AUR890G630

Burner controller developed as an upgrade for the RA890 ProtectoRelay; with an AUD100/110/120 advanced ultraviolet flame detector it automatically executes ignition, flame monitoring, and fuel shutoff for batch-operated gas or oil burners.

Technical Specifications

MassApprox. 600 g including the sub-base; approx. 1200 g with the Q890A100 replacement base unit
InputNon-voltage contact input, allowable contact resistance 500 ohm max. (low voltage temperature controller, contact reset)
ModelAUR890G630
MountingDIN rail or direct mounting through base screw holes; vertical or horizontal, but in horizontal mounting the 7-segment display must face directly upward
ApplicationBatch-operated combustion systems burning gas, oil or a gas/oil mixture
ApplicationsApplied in batch-operated combustion systems burning gas, oil, or gas/oil mixtures, such as industrial boilers, furnaces, and process heaters, where automatic ignition sequencing and flame failure lockout are required.
Key featuresModel decoding AUR890G630: G = UV detector version, 6 = 220 V AC supply, 3 = flame failure response 3 ± 1 s at 3 V DC flame voltage, 0 = no additional processing.; Lockout timing 13.5 ± 1.5 s; on ignition failure or flame failure the controller locks out and requires manual reset.; False flame detection time 15 s; reset timing 1 s or longer via reset switch or contact reset input.; Main burner combustion standby 0.4 s; 7-segment LED display shows sequence steps, alarm codes, and flame voltage.; Contact ratings: ignition transformer 360 VA, pilot valve 200 VA, main valve 200 VA, alarm 75 VA (per 120 V model specification).; Operating ambient temperature -20 to +60 °C; protective structure IP40 with sideboard; overvoltage category II, pollution degree 2.; Complies with JIS C 9730-2-5; UL Listed (UL 60730-2-5) and FM Approved (FM 7610) for certified models; CE marked per Azbil literature.; Designed for external prepurge instrumentation; usable with a replacement base unit Q890A100 when upgrading from RA890.
Reset timing1 s or longer (reset switch or contact reset input); reset input not accepted when no alarm has occurred
Service life10 years at 8 hours per day, or 100,000 start/stop cycles (at 25 deg C, room humidity, rated voltage)
Case materialDenatured PPE resin (UL94-V0 PTI material group IIIa), black
Lockout timing13.5 ± 1.5 s
Pollution degreePD2
Product categoryIndustrial combustion component - burner controller (upgrade of the RA890 ProtectoRelay)
Shock resistance0 to 9.8 m/s2 during operation; 0 to 300 m/s2 during transport/storage
Storage humidity5 to 95 %RH (no condensation)
Operating voltage220 V AC, 50/60 Hz
Power consumption10 W or less
Protection ratingIP40 with sideboards 81447515-001 fitted to the sub-base BC-R05A100; IP10 with only the Q890A100 base unit or the bare sub-base
Rated power supply220 V AC, 50/60 Hz (100 / 200 / 220 V AC depending on model)
Dielectric strength1500 V AC for 1 min or 1800 V AC for 1 s between each terminal (except flame detector terminals 14, 15) and ground (the DIN rail clamp)
Flame establishment1.5 to 4.5 V DC (AUD100/110/120 UV sensor)
Flame out detection0.2 to 0.6 V DC (AUD100/110/120 UV sensor)
Storage temperature-20 to +70 deg C
Contact rating alarm75 VA
Overvoltage categoryII
Standards complianceJIS C 9730-2-5:2010
Vibration resistance0 to 3.2 m/s2 during operation; 0 to 9.8 m/s2 during transport/storage (10 to 150 Hz)
Insulation resistance50 Mohm min. with a 500 V DC megger between each terminal (except terminals 14, 15) and ground
Operating temperature-20 to +60 °C
Flame failure response3 ± 1 s (UV sensor, at 3 V DC flame voltage)
Contact rating main valve200 VA
Recommended flame voltageStable 2 V DC or above
Contact rating pilot valve200 VA
False flame detection time15 s
Flame voltage output range0.2 to 4.5 V DC (UV sensor)
Operating ambient humidity10 to 90 %RH (no condensation)
Operation at flame failureLockout
Operating ambient temperature-20 to +60 deg C
Operation at ignition failureLockout
Allowable power supply voltage85 to 110 % of rated power supply
Main burner combustion standby0.4 s
Contact rating ignition transformer300 VA (100/200/220 V AC models); 360 VA on the AC120 V model AUR890G330
Ignition wait time from start check3 +/-0.3 s (per the AC120 V specification CP-SS-1924E)

Burner control: purchasing checks

Review these fields for the complete ordering code. Unconfirmed fields can be included with your enquiry.

Operating voltage
220 V AC, 50/60 Hz
Operating sequence
To be confirmed for the exact model
Flame supervision
To be confirmed for the exact model
Operating mode
To be confirmed for the exact model
Wiring / base
To be confirmed for the exact model
Program / configuration
To be confirmed for the exact model

Supply information

The quotation confirms the actual items, accessories and commercial terms for your order.

Item condition
To be confirmed in your quotation
Packaging
To be confirmed in your quotation
Included accessories
To be confirmed in your quotation
Stock confirmation
To be confirmed in your quotation
Dispatch / lead time
To be confirmed in your quotation
Price conditions
To be confirmed in your quotation
Warranty provider
To be confirmed in your quotation

More components in this catalog