ModelVGD40.125L
ConnectionFlanged, PN16 to ISO 7005-2
Net weight18200 g
ApplicationsTypical applications include gas trains of forced draft gas burners, industrial boilers and process heating systems requiring dual shut-off redundancy, in connection with SKP15 for shut-off or SKP25, SKP55 or SKP75 for pressure or ratio control.
Key featuresTwo valve sections in one body, Requires two matching SKPx5 actuators for operation
Nominal sizeDN125
Order numberBPZ:VGD40.125L
Product typedouble gas valve body
Product categoryIndustrial combustion component - Class A double gas valve (safety shut-off valve for gas trains, 'L' variant with inverted mounting plates)
Flow rate at 1kpa630 m³/h (air)
Valve configurationInverted mounting plate position
Application scenariosGas-train installations in commercial and industrial burner systems.
Volume between valves5.2 litres
Max operating pressure70 kPa
Air flow at 1 kPa pressure drop630 m³/h