ModelVGD40.065L
Net weight8400 g
ApplicationsIt is installed in gas trains of forced-draft gas burners, industrial boilers and combustion plants requiring redundant safety shut-off or integrated pressure/air-gas ratio control; the L version suits layouts where the inverted mounting-plate position is required.
Key featuresTwo valve sections in one body, Requires two matching SKPx5 actuators for operation
Nominal sizeDN65 (PN16 flanges to ISO 7005-2)
Product typedouble gas valve body
Product categoryIndustrial combustion component - Class A double gas valve (safety shut-off valve for gas trains)
Flow rate at 1kpa160 m3/h (air)
Medium temperature-15 to +60 C
Application scenariosGas-train installations in commercial and industrial burner systems.
Max operating pressure70 kPa
Permissible back pressure30 kPa (against direction of flow)