ModelQRA73.A27
Net weight700 g
Sensitivitynormal
ApplicationsTypical uses are continuous flame supervision on gas and oil burners of medium to large industrial boilers, process heaters and multi-burner plants managed by LMV5 systems, where periodic shutter self-testing supports uninterrupted safe operation.
Key featuresExact variant per the official type summary: normal sensitivity, 125 mm detector tube, AC 230 V (+10%/-15%); spare UV tube AGR 4 502 4065 0.; Built for continuous operation with Siemens LMV5-series burner management systems; delivered complete with mounting clamp and used with an AGM23 connecting cable.; A swiveling shutter driven by an integral stepper motor and a quartz-glass window protect the UV cell and enable automatic self-check cycles.; Degree of protection IP65; ambient temperature -20 to +60 degrees Celsius; average UV cell service life about 10,000 hours at maximum 50 degrees Celsius.; Weight approximately 700 g; mounts directly, on a viewing tube or on a combustion-chamber sight port using the AGG16.C adapter.
Order numberBPZ:QRA73.A27
Product typeUV flame detector
Operating modeContinuous
Product categoryIndustrial combustion component - self-checking UV flame detector for continuous operation
Uv spectral band190-270 nm
Operating voltageAC 230 V (+10%/-15%)
Ambient temperature-20 to +60 C
Degree of protectionIP65
Detector tube length125 mm
Uv cell service lifeapprox 10,000 h at max 50 C