ModelQRA55.G17
SensitivityHigh
ApplicationsTypical applications include industrial and commercial gas- or oil-fired burners, boilers and process heating systems supervised by LGK16... or LGI16... burner controls, where continuous flame supervision and high detection sensitivity are required.
Key featuresHigh sensitivity model with a 69 mm detector tube and AC 100...110 V mains voltage; spare UV tube AGR 4 502 4065 0.; UV-sensitive cell with two electrodes ignites when illuminated with radiation in the 190...270 nm range, triggering a current in the flame detector circuit.; The UV cell does not respond to glowing firebrick in the combustion chamber, daylight or boiler-room illumination, reducing false signals.; Self-checking design: the UV cell sits behind a swiveling shutter at the front end of the detector tube, driven by a stepper motor in the housing.; Degree of protection IP65; permissible operating temperature -20...+60 °C and humidity below 95% r.h.; Average UV cell life approximately 10,000 hours at a maximum of 50 °C; higher ambient temperatures reduce the lifetime considerably.; Delivered complete with clamp for direct mounting; electrical connection requires the AGM19 connecting cable (2 m).
Order numberBPZ:QRA55.G17
Product typeUltraviolet flame detector
Spare uv tubeAGR 4 502 4065 0
Operating modeContinuous
Flame detectionUltraviolet
Product categoryUltraviolet flame detector
Operating voltage100–110 V AC
Degree of protectionIP65
Detector tube length69 mm
Rated supply voltage100-110 V AC
Detector tube length mm69 mm
Uv cell average lifetimeapprox. 10,000 h at max. 50 °C
Operating temperature range-20...+60 °C