ModelQRA2M
SensitivityHigh
ApplicationsTypical applications include flame supervision for intermittently operating oil or gas burners in boilers, furnaces and process heating plants, mounted directly on the burner and connected to the burner control via the appropriate adapter.
Key featuresHigh sensitivity version of the QRA2 series; supplied without flange or clamp, with green terminal cover and spare UV tube AGR 4 502 4065 0.; For use with LGB2..., LFL..., LFE1..., LFE10..., LMG..., LME21/22/39..., LME7... and LMV2/3/5... burner controls in intermittent operation.; Degree of protection IP40 with adequate cable entry (e.g. AGG09); safety class II; weight approx. 46 g.; Permissible combustion chamber pressure max. 50 mbar; UV cell does not respond to glowing firebrick, daylight or boiler room illumination.; Plastic housing metalized to prevent static charging; ignition cable supplied by the customer, recommended H05VV-F 2 x 0.75 mm2.
Product typeUV flame detector
Spare uv tubeAGR 4 502 4065 0
Terminal coverGreen
Product categoryIndustrial combustion component - UV flame detector (flame supervision for intermittently operating burners)
Ambient temperature-20...+60 degrees C
Degree of protectionIP40
Perm combustion chamber pressuremax. 50 mbar