Skip to content
Industrial combustion components support@rifuze.com

Siemens

Siemens LMV36.300A2 burner management system

Siemens LMV36.300A2 · view 1
Model
LMV36.300A2

Get a quote

Siemens · LMV36.300A2

LMV36.300A2 integrates burner sequencing, flame supervision, gas-valve proving, and electronic fuel-air positioning in one basic unit. It coordinates the combustion-air and fuel actuators, evaluates safety inputs, supervises operating states, and initiates safety shutdown or lockout when the programmed conditions are not satisfied.

Technical Specifications

ModelLMV36.300A2
Fan controlVariable-frequency-drive interface
ApplicationsIntended for staged or modulating forced-draught gas, oil, or dual-fuel burners whose component set is approved for the LMV3 platform. Gas and oil can be used in intermittent operation; continuous operation has stricter gas-and-ionization conditions described by Siemens. Burner engineering must validate actuator direction, curves, valve proving, detector selection, purge times, parameter access, and all safety interlocks.
Key featuresThe A2 ordering variant is a 230 V AC unit with the European parameter set for compatible forced-draught burner applications.; Electronic fuel-air ratio control supports up to two compatible SQM3 or SQN1 actuators.; Compatible flame-detection options include ionization, QRB, QRC, QRA2, QRA4 and QRA10 devices, subject to the stated operating-mode restrictions.; Integrated interfaces provide variable-frequency-drive fan control, Modbus communication, and the Siemens BCI connection for display or service tools.; Configuration and diagnostics can be performed with a compatible operator display or Siemens ACS410 software by qualified commissioning personnel.
Product typeburner management system
Parameter setEuropean
Valve provingIntegrated
CommunicationsModbus and Siemens BCI
Product categoryMicroprocessor burner management system with electronic fuel-air ratio control.
Designed lifetime250,000 burner start cycles or approximately 10 years under stated conditions
Operating voltageAC 230 V
Fuel air actuatorsUp to 2 compatible SQM3 or SQN1 actuators
Product dimensionsWidth 230 mm; height 135 mm; depth 60 mm
Flame detector optionsIonization, QRB, QRC, QRA2, QRA4, QRA10

Supply information

The quotation confirms the actual items, accessories and commercial terms for your order.

Item condition
To be confirmed in your quotation
Packaging
To be confirmed in your quotation
Included accessories
To be confirmed in your quotation
Stock confirmation
To be confirmed in your quotation
Dispatch / lead time
To be confirmed in your quotation
Price conditions
To be confirmed in your quotation
Warranty provider
To be confirmed in your quotation