ModelLMV36.300A2
Fan controlVariable-frequency-drive interface
ApplicationsIntended for staged or modulating forced-draught gas, oil, or dual-fuel burners whose component set is approved for the LMV3 platform. Gas and oil can be used in intermittent operation; continuous operation has stricter gas-and-ionization conditions described by Siemens. Burner engineering must validate actuator direction, curves, valve proving, detector selection, purge times, parameter access, and all safety interlocks.
Key featuresThe A2 ordering variant is a 230 V AC unit with the European parameter set for compatible forced-draught burner applications.; Electronic fuel-air ratio control supports up to two compatible SQM3 or SQN1 actuators.; Compatible flame-detection options include ionization, QRB, QRC, QRA2, QRA4 and QRA10 devices, subject to the stated operating-mode restrictions.; Integrated interfaces provide variable-frequency-drive fan control, Modbus communication, and the Siemens BCI connection for display or service tools.; Configuration and diagnostics can be performed with a compatible operator display or Siemens ACS410 software by qualified commissioning personnel.
Product typeburner management system
Parameter setEuropean
Valve provingIntegrated
CommunicationsModbus and Siemens BCI
Product categoryMicroprocessor burner management system with electronic fuel-air ratio control.
Designed lifetime250,000 burner start cycles or approximately 10 years under stated conditions
Operating voltageAC 230 V
Fuel air actuatorsUp to 2 compatible SQM3 or SQN1 actuators
Product dimensionsWidth 230 mm; height 135 mm; depth 60 mm
Flame detector optionsIonization, QRB, QRC, QRA2, QRA4, QRA10