ModelLME75.000A2
Net weight490 g
ApplicationsTypical applications are multistage or modulating oil and gas forced draft burners and atmospheric burners on industrial boilers, process plants and heating systems requiring robust flame safeguard control.
Key featuresMicroprocessor-based basic unit for burners of medium to high capacity in intermittent operation; needs a matching program module and display unit for full functionality.; Operates on AC 230 V mains (A2 version) at 50/60 Hz, with power consumption below 10 W typically; external primary fuse max 6.3 A slow.; Flame supervision via ionization probe or UV flame detectors QRA2/QRA4/QRA10; applications conforming to EN 267, EN 676 and EN 746-2.; Type-tested and approved in accordance with DIN EN 298; safety class I to DIN EN 60730-1; degree of protection IP00 in panel installation.; Features undervoltage detection, electrical remote reset, multicolor LED fault indication and air pressure supervision with function check.; Designed lifetime of 250,000 burner startup cycles.
Product typeburner control
Safety classI (DIN EN 60730-1)
Mains frequency50/60 Hz
Product categoryIndustrial combustion control - Microprocessor-based burner control (flame safeguard)
Operating voltageAC 230 V
Power consumption< 10 W typical
Product dimensionsWidth 120 mm; height 180 mm; depth 53 mm
Degree of protectionIP00
Application scenariosSupervision of multistage or modulating forced-draft oil and gas burners; applications include industrial thermoprocessing equipment in accordance with EN 746-2. Actual burner functions depend on the separately ordered PME75 program module and its configuration.
External primary fusemax. 6.3 A slow