ModelLFL1.635
Net weight1000 g
ApplicationsUsed on gas, oil or dual-fuel forced-draught burners for industrial boilers, process heating systems, stationary air heaters and other high-capacity combustion plant requiring an extended pre-purge period before ignition.
Key featuresMains AC 230 V (-15%/+10%), 50-60 Hz; power consumption approx. 3.5 VA; IP40, safety class II.; Variant-specific program times at 50 Hz: pre-purge t1 = 66 s, ignition safety time TSA = 2.5 s (first safety time TSA' = 5 s).; For direct spark flame or interrupted pilot burner construction; 01-series control with long purge suited to high-capacity burners.; Flame supervision via UV detectors QRA2, QRA4 or QRA10, or an ionization probe.; Checked air damper control with separate actuator OPEN, CLOSE and MIN outputs; remote lockout warning, reset and emergency shutdown facilities.; Automatic self-test of the flame supervision circuit; designed lifetime of 250,000 burner startup cycles.; Type-tested to DIN EN 298 and CE marked; plug-in design.
Product typeburner control
Mains frequency50-60 Hz
Prepurge time t166 s (at 50 Hz)
Product categoryIndustrial combustion component - burner control (program controller) for forced-draught gas, oil or dual-fuel burners
Operating voltageAC 230 V (-15%/+10%)
Power consumptionapprox. 3.5 VA
Product dimensionsWidth 103 mm; height 109 mm; depth 103 mm
Ignition safety time tsa2.5 s