ModelLFL1.122
Net weight1000 g
ApplicationsIt is used on forced-draft gas burners of medium capacity, especially flash steam generators, stationary air heaters and dual-fuel plants in intermittent operation, where reliable sequence control, flame supervision and lockout protection are required.
Key featuresType LFL1.122 (02 series), article no. BPZ:LFL1.122; prepurge time t1 10 s, ignition safety time TSA 2 s and postpurge time t6 10 s at 50 Hz.; Mains voltage AC 230 V -15%/+10%, 50...60 Hz +/-6%; AC 100...110 V version available by adding the suffix -110 V when ordering.; Power consumption approximately 3.5 VA; weight approximately 1000 g; degree of protection IP40; safety class II; designed lifetime 250,000 burner startup cycles.; Flame supervision circuit is automatically checked during each startup; a built-in exchangeable unit fuse protects the control contacts.; Approved to DIN EN 298; certifications include SP, GL, DIN, DVGW and TUV, and it is CE marked under EU Gas Appliances Regulation 2016/426.
Order numberBPZ:LFL1.122
Product typeburner control
Prepurge time t110 s
Product categoryIndustrial combustion component - flame supervisor (burner control) for forced-draft gas burners
Operating voltageAC 230 V (-15%/+10%), 50-60 Hz
Power consumptionapprox 3.5 VA
Product dimensionsWidth 103 mm; height 109 mm; depth 103 mm
Degree of protectionIP40
Ignition safety time tsa2 s