ModelLEC18853
ApplicationsApplicable to legacy industrial combustion systems that already specify LEC1/8853 for double- or multi-flame supervision, expanding-flame or interrupted-pilot arrangements, and oil, gas, or dual-fuel duty. Because the product is a legacy platform, replacement work should start from the burner schematic and approval file. Voltage, timer settings, base, safeguards, detectors, valve sequence, purge logic, and continuous-operation conditions must match.
Key featuresThe LEC1/8853 ordering variant is rated for 220 to 240 V AC at 50 Hz.; Its factory timing set is 30 seconds for prepurge t1, 2 seconds for the first safety time TSA, and 2 seconds for t9.; The sequence can control the fan motor, flue-gas fan, air damper, ignition transformer, one to three fuel valves, load controller, and external fault indication.; Separate LAE10, LFE10, or LFE50 flame safeguards are used according to the detector and burner arrangement documented by Siemens.; The unit is delivered without its terminal base, which must be selected and ordered separately for the installation.
Built in fuseT6.3H250V
External fuse10 A slow maximum
Terminal baseNot included
Operating modeContinuous or intermittent with the prescribed separate flame safeguards
Product statusDiscontinued
Factory time t92 s
Mains frequency50 Hz
Product categoryLegacy burner sequencing control for double- or multi-flame supervision systems.
Operating voltageAC 220 to 240 V
Factory safety time tsa2 s
Factory prepurge time t130 s
Documented ordering designationLEC1/8853