The TC checks whether the safety valves in a gas train are sufficiently tight before burner start-up or after shutdown. It tests the valves and the enclosed space between them. An inadmissible leak prevents the burner from being enabled. When the required test is completed successfully, the device provides an enable signal to the connected burner control, which can then proceed with its operating sequence.
Technical Specifications
ModelTC1C05WW
ApplicationsValve proving on industrial thermoprocessing equipment and boiler gas trains.; Gas safety installations on forced-draught burners that require the valve assembly to pass a tightness test before burner enable.
Key featuresThe testing arrangement is designed for a system with two safety valves. Its purpose is to detect a leaking valve while the other valve provides the remaining shutoff barrier.; Mounting and test-gas handling depend on the device version. TC 1V attaches to valVario controls, while TC 1C is intended for the specified CG combination controls.; The supply voltage and control voltage are separate ordering characteristics. Their values must match the installed burner control circuit and the complete TC designation.
Product categoryValve tightness control for two-valve gas safety systems
Model configurationThis is the version for the specified CG combination controls.; The 05 pressure class specifies a maximum inlet pressure of 500 mbar.; The supply is 230 V AC and the control voltage is 230 V AC.
Supply information
The quotation confirms the actual items, accessories and commercial terms for your order.
- Item condition
- To be confirmed in your quotation
- Packaging
- To be confirmed in your quotation
- Included accessories
- To be confirmed in your quotation
- Stock confirmation
- To be confirmed in your quotation
- Dispatch / lead time
- To be confirmed in your quotation
- Price conditions
- To be confirmed in your quotation
- Warranty provider
- To be confirmed in your quotation