ModelVR8205M2914
ApplicationsUsed in natural gas direct ignition heating appliances, including LB White Guardian forced-air furnace heaters for poultry houses and livestock buildings, as well as furnaces, boilers and space heaters requiring a compact dual automatic combination gas control.
Key features24 Vac, 60 Hz supply with 0.5 A current draw and 1/2 in. x 1/2 in. NPT straight-through body.; Natural gas version of the VR8205M standard-opening control, OEM number VR8205M2914/B.; Factory regulator setting 3.5 in. wc for natural gas; -40 F to +175 F (-40 C to +79 C) ambient rating and 1/2 psi (3.5 kPa) inlet pressure rating.; Capacity rated at 150 cfh (4.2 m3/h) at 1 in. wc pressure drop, with 20,000 to 200,000 Btuh regulated range.; Terminal block color-coded brown for direct ignition; 1/4 in. male quick-connect terminals.; OEM gas valve for LB White Guardian natural gas forced-air furnace heaters.
Connection size1/2 in x 1/2 in NPT straight-through
Product categoryResidential/light-commercial gas control - direct ignition dual automatic valve combination gas control
Operating voltage24 Vac, 60 Hz
Max inlet pressure1/2 psi (3.5 kPa)
Capacity at 1 in wc150 cfh (4.2 m3/h)