ModelRM7898A1000
Fusing15 A type SC fast-blow fuse (or equivalent)
Net weight900 g
ApplicationsSuitable for gas, oil or combination fuel single-burner power burner applications in industrial boilers, process combustion equipment and similar plants where automatic valve seat leakage testing and proof of closure are desirable.
Key featuresValve Proving System verifies effective closure of the double safety shut-off valves each burner cycle; scheduled Never, Before, After, Both or Split via the S7800A1142 keyboard display module.; Interrupted pilot with a 10 second pilot flame establishing period as received; intermittent pilot operation available when terminal 19 is powered; 10 second main flame establishing period.; Preignition interlock (proof of closure) input on terminal 20 and shutter-driven output (terminal 22) for dynamic self-checking amplifiers such as R7861A, R7886A and R7851C.; Blinking fault code POWER LED annunciation on safety shutdown and programmable postpurge time up to 60 minutes.; Selectable running or lockout interlock; recycle or lockout action on flame failure; VPS demand input on terminal 17 and direct spark ignition enable on terminal 18.; 120 Vac (+10%/-15%), 50/60 Hz supply; 10 W maximum power dissipation; 2000 VA maximum connected load; SIL 3 Capable in a properly designed Safety Instrumented System.
Shutter output120 Vac, 0.5 A
Product categoryBurner control module
Operating voltage120 Vac (+10%/-15%), 50/60 Hz (+/-10%)
Power dissipation10 W maximum
Max connected load2000 VA
Operating temperature-40 deg C to +60 deg C
Main flame establishing period10 s
Pilot flame establishing period10 s interrupted as received; intermittent when terminal 19 energized