ModelRM7895B1013
Fusing15 A type SC fast-blow fuse (or equivalent)
Prepurgeselectable 2 s to 30 min via ST7800A purge card
Net weight900 g
ApplicationsUsed in commercial and industrial gas, oil or combination fuel single-burner plants requiring prepurge and airflow proving, including boilers, furnaces, ovens, kilns and packaged burner systems.
Key featuresDynamic airflow switch check (AFSC) feature verifies the airflow interlock during the prepurge sequence; airflow interlock on terminal 7 rated 8 A run and 43 A inrush.; Dedicated burner motor (blower) output on terminal 4 rated 9.8 A full load with 58.8 A locked rotor inrush.; Selectable 4 or 10 second pilot flame establishing period; intermittent pilot valve on terminal 8.; Selectable prepurge timing from two seconds to 30 minutes using the plug-in ST7800A purge timer card, which is required for operation.; Interchangeable plug-in flame amplifiers provide 0.8 or 3 second flame failure response time; selectable recycle or lockout on loss of airflow.; 120 Vac (+10%/-15%), 50/60 Hz supply; 10 W maximum power dissipation; 2000 VA maximum connected load; SIL 3 Capable; -40 deg C to +60 deg C operating ambient.
Product categoryIndustrial combustion safety component - microprocessor-based on/off integrated burner control relay module with airflow switch check and purge timer (7800 Series, flame safeguard)
Operating voltage120 Vac (+10%/-15%), 50/60 Hz (+/-10%)
Power dissipation10 W maximum
Max connected load2000 VA
Burner motor output120 Vac, 9.8 A full load, 58.8 A locked rotor inrush
Airflow switch checkyes (dynamic airflow switch check during prepurge)
Operating temperature-40 deg C to +60 deg C
Pilot flame establishing period4 or 10 s (selectable)