ModelRM7895A1014
Fusing15 A type SC fast-blow fuse (or equivalent)
Prepurgeselectable 2 s to 30 min via ST7800A purge card
Net weight900 g
ApplicationsUsed in commercial and industrial gas, oil or combination fuel single-burner plants requiring prepurge, including boilers, furnaces, ovens, kilns and packaged burner systems.
Key featuresDedicated burner motor (blower) output on terminal 4 rated 9.8 A full load with 58.8 A locked rotor inrush.; Selectable 4 or 10 second pilot flame establishing period; intermittent pilot valve on terminal 8.; Selectable prepurge timing from two seconds to 30 minutes using the plug-in ST7800A purge timer card, which is required for operation.; Interchangeable plug-in flame amplifiers provide 0.8 or 3 second flame failure response time depending on the amplifier selected.; 120 Vac (+10%/-15%), 50/60 Hz supply; 10 W maximum power dissipation; 2000 VA maximum connected load; 15 A type SC fuse.; Nonvolatile memory retains history files and sequencing status after power loss; SIL 3 Capable in a properly designed Safety Instrumented System.
Product categoryIndustrial combustion safety component - microprocessor-based on/off integrated burner control relay module with purge timer (7800 Series, flame safeguard)
Operating voltage120 Vac (+10%/-15%), 50/60 Hz (+/-10%)
Power dissipation10 W maximum
Max connected load2000 VA
Burner motor output120 Vac, 9.8 A full load, 58.8 A locked rotor inrush
Operating temperature-40 deg C to +60 deg C
Pilot flame establishing period4 or 10 s (selectable)