Fuelgas only
ModelRM7890B1048
Fusing15 A type SC fast-blow fuse (or equivalent)
Net weight800 g
ApplicationsDesigned for gas-fired atmospheric burners and single-burner commercial or industrial combustion equipment requiring valve seat leakage testing, proof of closure and shutter-driven self-checking detectors.
Key featuresValve Proving System verifies closure of the double gas valve seats in Standby; scheduled Never, Before, After, Both or Split at commissioning.; Preignition interlock (proof of closure switch) input on terminal 20; selectable intermittent or interrupted pilot function via jumper JR3.; Selectable 4 or 10 second pilot flame establishing period and a 10 second main flame establishing period; Run/Test switch for interrupted pilot setup.; Shutter drive output on terminal 22 (120 Vac, 0.5 A) for dynamic self-checking ultraviolet flame detectors (RM7890B feature).; Blinkum fault annunciation on safety shutdown; built-in features configured only through the optional S7800A1142 display; selectable relight or lockout upon main flame failure.; 120 Vac (+10%/-15%), 50/60 Hz supply; 10 W maximum power dissipation; 2000 VA maximum connected load; 15 A type SC fuse; -40 deg C to +60 deg C operating ambient.
Shutter output120 Vac, 0.5 A
Product categoryIndustrial combustion safety component - microprocessor-based on/off primary burner control relay module with Valve Proving System and shutter drive for atmospheric gas burners (7800 Series, flame safeguard)
Operating voltage120 Vac (+10%/-15%), 50/60 Hz (+/-10%)
Power dissipation10 W maximum
Max connected load2000 VA
Operating temperature-40 deg C to +60 deg C
Main flame establishing period10 s
Pilot flame establishing period4 or 10 s (selectable)