ModelRM7890B1030
Fusing15 A type SC fast-blow fuse (or equivalent)
Net weight800 g
ApplicationsTypical applications include on/off gas, oil or combination fuel single burner systems in commercial and industrial boilers, furnaces, ovens, kilns and other combustion plants requiring a microprocessor-based flame safeguard relay.
Key featuresFixed 10 second pilot flame establishing period (PFEP), per the sequence chart; the full PFEP is completed before the main fuel valve is energized.; Shutter drive output on terminal 22 (120 Vac, 0.5 A) for dynamic self-checking ultraviolet flame detectors, available on the RM7890B variant.; Intermittent pilot valve on terminal 8; ignition on terminal 10 is de-energized once flame is proven.; Selectable relight or lockout action on flame failure via site-configurable jumper JR2.; Sequence status LEDs, optional keyboard display module, Data ControlBus and remote reset capability; nonvolatile memory retains history after power loss.; 120 Vac (+10%/-15%), 50/60 Hz supply; 10 W maximum power dissipation; 2000 VA maximum connected load; -40 deg C to +60 deg C operating ambient; SIL 3 Capable.
Shutter output120 Vac, 0.5 A
Product categoryBurner control module
Operating voltage120 Vac (+10%/-15%), 50/60 Hz (+/-10%)
Power dissipation10 W maximum
Max connected load2000 VA
Storage temperature-40 deg C to +66 deg C
Operating temperature-40 deg C to +60 deg C
Pilot flame establishing period10 s fixed