ModelRM7890B1014
Fusing15 A type SC fast-blow fuse (or equivalent)
Net weight800 g
ApplicationsTypical applications include on/off gas, oil or combination fuel single burner systems in commercial and industrial boilers, furnaces, ovens, kilns and other combustion plants requiring a microprocessor-based flame safeguard relay with shutter-driven detector support.
Key featuresShutter drive output on terminal 22 (120 Vac, 0.5 A) for dynamic self-checking ultraviolet flame detectors, available on the RM7890B variant.; Selectable 4 or 10 second pilot flame establishing period via site-configurable jumper JR1; intermittent pilot valve on terminal 8.; Selectable relight or lockout action on flame failure via jumper JR2 (relight requires a 0.8 second flame failure response time amplifier).; Safe start check, closed loop logic test, dynamic self-check logic and dynamic input check provide enhanced safety shutdown responses.; Sequence status LEDs (POWER, PILOT, FLAME, MAIN, ALARM), optional keyboard display module, Data ControlBus and remote reset capability.; 120 Vac (+10%/-15%), 50/60 Hz supply; 10 W maximum power dissipation; 2000 VA maximum connected load; -40 deg C to +60 deg C operating ambient; SIL 3 Capable.
Shutter output120 Vac, 0.5 A
Product categoryBurner control module
Operating voltage120 Vac (+10%/-15%), 50/60 Hz (+/-10%)
Power dissipation10 W maximum
Max connected load2000 VA
Storage temperature-40 deg C to +66 deg C
Operating temperature-40 deg C to +60 deg C
Pilot flame establishing period4 or 10 s (selectable via JR1)