Fuelgas only
ModelRM7890A1056
Fusing15 A type SC fast-blow fuse (or equivalent)
Net weight800 g
ApplicationsDesigned for gas-fired atmospheric burners and single-burner commercial or industrial combustion equipment such as boilers and process heating systems where valve seat leakage testing and proof of closure are desirable.
Key featuresValve Proving System tests the seat integrity of the double gas valve arrangement to verify closure in Standby; scheduled Never, Before, After, Both or Split at commissioning.; Preignition interlock (proof of closure switch) input on terminal 20; selectable intermittent or interrupted pilot function via jumper JR3.; Selectable 4 or 10 second pilot flame establishing period and a 10 second main flame establishing period; Run/Test switch for interrupted pilot setup.; Blinkum fault annunciation on safety shutdown (POWER LED blinks a fault code); built-in features configured only through the optional S7800A1142 display.; Selectable relight or lockout action upon main flame failure; MV2 valve proving output on terminal 17.; 120 Vac (+10%/-15%), 50/60 Hz supply; 10 W maximum power dissipation; 2000 VA maximum connected load; 15 A type SC fuse; -40 deg C to +60 deg C operating ambient.
Product categoryIndustrial combustion safety component - microprocessor-based on/off primary burner control relay module with Valve Proving System for atmospheric gas burners (7800 Series, flame safeguard)
Operating voltage120 Vac (+10%/-15%), 50/60 Hz (+/-10%)
Power dissipation10 W maximum
Max connected load2000 VA
Operating temperature-40 deg C to +60 deg C
Main flame establishing period10 s
Pilot flame establishing period4 or 10 s (selectable)