ModelRM7890A1031
Fusing15 A type SC fast-blow fuse (or equivalent)
Net weight800 g
ApplicationsTypical applications include on/off gas, oil or combination fuel single burner systems in commercial and industrial boilers, furnaces, ovens, kilns and other combustion plants where a proven microprocessor-based flame safeguard relay with automatic sequencing is required.
Key featuresFixed 30 second pilot flame establishing period (PFEP), not affected by the JR1 jumper; intermittent pilot valve on terminal 8 and ignition on terminal 10.; Selectable relight or lockout action on flame failure via site-configurable jumper JR2 (relight requires a 0.8 second flame failure response time amplifier).; Safe start check, closed loop logic test, dynamic self-check logic and dynamic input check provide enhanced safety shutdown responses.; Sequence status LEDs (POWER, PILOT, FLAME, MAIN, ALARM), optional keyboard display module, Data ControlBus and remote reset capability.; 120 Vac (+10%/-15%), 50/60 Hz supply; 10 W maximum power dissipation; 2000 VA maximum connected load; 15 A type SC fuse.; Rated for -40 deg C to +60 deg C operating ambient, 85% RH noncondensing humidity and 0.5G vibration; SIL 3 Capable in a properly designed Safety Instrumented System.
Product categoryIndustrial combustion safety component - microprocessor-based on/off integrated burner control relay module (7800 Series, flame safeguard)
Operating voltage120 Vac (+10%/-15%), 50/60 Hz (+/-10%)
Power dissipation10 W maximum
Max connected load2000 VA
Storage temperature-40 deg C to +66 deg C
Operating temperature-40 deg C to +60 deg C
Pilot flame establishing period30 s fixed