ModelRM7840G1022
Fusing15 A type SC fast-blow fuse (or equivalent)
Net weight700 g
Post purgeprogrammable up to 60 min (default 15 s)
ApplicationsTypical applications include gas, oil or combination fuel modulating power burners on commercial and industrial boilers, process heaters and furnaces where valve proving and programmable purge are required for enhanced safety.
Key featuresValve Proving System detects leaks greater than 0.1% of burner input capacity; the test can be scheduled Never, Before, After, Both or Split via the keyboard display.; Low-high-low firing rate control with low fire proven purge (LHL-LF Proven); requires the S7800A1142 keyboard display for VPS setup and post purge adjustment.; 4 or 10 second pilot flame establishing period and 10, 15 or 30 second or intermittent main flame establishing period.; Programmable post purge up to 60 minutes (shipped with 15 seconds) using the keyboard display.; 120 Vac (+10%/-15%), 50/60 Hz supply; 10 W maximum power dissipation; 2000 VA maximum connected load; 15 A type SC fusing.; Running and preignition interlocks; prepurge determined by the plug-in purge timer card; five sequence LEDs and nonvolatile fault history.; UL Listed (File No. MP268), CSA Certified (LR95329-3), FM Approved, Swiss Re acceptable, FCC Part 15 Class B and SIL 3 Capable.
Product categoryBurner control module
Operating voltage120 Vac (+10%/-15%), 50/60 Hz (+/-10%)
Power dissipation10 W maximum
Max connected load2000 VA
Operating temperature-40 deg C to +60 deg C
Main flame establishing period10 s, 15 s, 30 s or intermittent
Pilot flame establishing period4 s or 10 s