ModelRM7838C1020
ApplicationsSupervising industrial modulating single-burner process heating systems firing gas, oil, coal, or combination fuel where semi-automatic manual start sequences and pilot hold capability are required.; Integration into safety instrumented process burner systems demanding SIL 3 capable flame safeguard control, proven high-fire and low-fire purge timing, and lockout-only safety alarm annunciation.
Key featuresOperates on 120 Vac power at 50/60 Hz with a maximum power dissipation of 10 watts and a total connected load rating of 2000 VA.; Provides a five-second main flame establishing period alongside selectable pilot flame establishing periods of four seconds or ten seconds.; Requires an ST7800C plug-in purge card, a Q7800 wiring subbase, and an R78-series plug-in flame amplifier offering none, AMPLICHECK, or dynamic self-check testing.; Features five sequence light-emitting diodes, nonvolatile memory retaining lockout status and diagnostic history files after power disruption, and test access for external voltage checks.; Achieves SIL 3 capability within a properly designed safety instrumented system.; Maintains environmental ratings from -40°F to +140°F (-40°C to +60°C) and handles continuous noncondensing relative humidity up to 85 percent.
Included displayS7800
Product categoryBurner control module
Operating voltage120 V AC (−15% / +10%)
Purge timing componentST7800C purge timer card
Compatible wiring subbasesQ7800A or Q7800B
Main flame establishing period options10 s or intermittent
Pilot flame establishing period options4 or 10 s