ModelRM7838A1014
Fusing20 A type FRN (or equivalent)
Net weight700 g
ApplicationsTypical applications include semi-automatically fired industrial boilers, process heating systems, kilns, ovens and furnaces with gas, oil or combination fuel single burner firing, where a manual-start control with purge and pilot-proving is required.
Key featuresIntermittent pilot valve operation; pilot flame must be proven before fuel is admitted to the main burner.; Selectable pilot flame establishing period (4 or 10 seconds) and selectable purge timing from 2 seconds to 30 minutes via the plug-in purge card.; 120 Vac (+10%/-15%), 50/60 Hz supply; 10 W maximum power dissipation; 2000 VA maximum connected load; 20 A type FRN fusing.; Includes the S7800A1142 keyboard display module with five sequence LEDs (POWER, PILOT, FLAME, MAIN, ALARM).; Purge hold until the high fire switch is proven with low fire position start; safety shutdown (lockout) with fault history stored in nonvolatile memory.; Rated for -40 deg C to +60 deg C operating ambient, 85% RH noncondensing humidity and 0.5G vibration.; UL Listed (File No. MP268, Guide MCCZ), CSA Certified (LR95329-3), FM Approved (J.I.1V9A0.AF), IRI acceptable and FCC Part 15 Class B.
Purge timing2 s to 30 min (selectable via plug-in purge card)
Product categoryBurner control module
Operating voltage120 Vac (+10%/-15%), 50/60 Hz (+/-10%)
Power dissipation10 W maximum
Max connected load2000 VA
Operating temperature-40 deg C to +60 deg C
Pilot flame establishing period4 s or 10 s (selectable)