ModelRM7823A1016
Fusing15 A type SC fast-blow fuse (or equivalent)
Net weight800 g
ApplicationsTypical applications include gas, oil, or combination fuel single burner systems in commercial and industrial boilers, furnaces, and process heaters where a separate flame detector relay is wired in series with a primary burner control to supervise the flame signal.
Key features120 Vac (+10%/-15%), 50/60 Hz supply; 10 W maximum power dissipation and 2000 VA maximum connected load with 15 A type SC fast-blow fusing.; Two SPDT dry-contact relay outputs rated 6 FLA/18 LRA at 120 Vac (normally open) and 1 A pilot duty at 120 Vac (normally closed).; Compatible with all 7800 SERIES plug-in flame amplifiers for rectification, ultraviolet, or infrared flame sensing.; Three sequence status LEDs (POWER, FLAME, ALARM), nonvolatile memory, and shutter drive output for dynamic self-check flame detectors.; SIL 3 Capable in a properly designed Safety Instrumented System when both normally open relay outputs are wired in series.; Rated for -40 deg C to +60 deg C operating ambient, 85% RH noncondensing humidity and 0.5G vibration; weighs approximately 0.8 kg.; UL Listed under ANSI/UL 60730-2-5 / CSA C22.2 No. 60730-2-5 (File MP268), FM Approved, Swiss Re acceptable, CE marked to the EU Gas Appliances Regulation, and EAC certified.
Output relaysTwo SPDT; N.O. 6 FLA/18 LRA at 120 Vac, N.C. 1 A pilot duty at 120 Vac
Product categoryFlame switch module
Operating voltage120 Vac (+10%/-15%), 50/60 Hz (+/-10%)
Power dissipation10 W maximum
Max connected load2000 VA
Operating temperature-40 deg C to +60 deg C