ModelRM7800G1018
Fusing15 A type SC fast-blow fuse (or equivalent)
Net weight700 g
Post purge15 s
ApplicationsTypical applications include gas or dual-fuel on/off power burners on commercial and industrial boilers, furnaces, ovens and process heaters where low fire proven purge with interrupted pilot sequencing is required.
Key featuresLow-high-low firing rate control with low fire proven purge (LHL-LF Proven); includes the S7800 keyboard display module.; Interrupted pilot with 4 or 10 second pilot flame establishing period; main flame establishing period selectable 10, 15 or 30 seconds or intermittent.; 120 Vac (+10%/-15%), 50/60 Hz supply; 10 W maximum power dissipation; 2000 VA maximum connected load; 15 A type SC fusing.; Post purge of 15 seconds; prepurge determined by the plug-in ST7800A purge timer card; running interlocks with preignition interlock.; Second stage pilot valve selectable and airflow check user selectable; 5 second early spark termination.; Five sequence LEDs, five-function Run/Test switch, nonvolatile memory and 0.5G vibration rating; operates from -40 deg C to +60 deg C.; UL Component Recognized (File No. MP268, Guide MCCZ), CSA Certified (LR95329-3), FM Approved (Report 1V9A0.AF), Swiss Re acceptable, FCC Part 15 Class B and SIL 3 Capable.
Product categoryIndustrial combustion safety component - microprocessor-based integrated burner control with low fire proven purge (7800 SERIES, on/off programmer)
Operating voltage120 Vac (+10%/-15%), 50/60 Hz (+/-10%)
Power dissipation10 W maximum
Max connected load2000 VA
Operating temperature-40 deg C to +60 deg C
Main flame establishing period10 s, 15 s, 30 s or intermittent
Pilot flame establishing period4 s or 10 s