ModelRM7800E1010
Fusing15 A type SC fast-blow fuse (or equivalent)
Net weight700 g
Post purge15 s
ApplicationsTypical applications include gas, oil or combination fuel on/off power burners on commercial and industrial boilers, furnaces, ovens and other combustion plants requiring proven low and high fire purge with interrupted pilot sequencing.
Key featuresLow-high-low firing rate control with both low fire and high fire proven purge (LHL-LF&HF Proven); includes the S7800 keyboard display module.; Interrupted pilot with 4 or 10 second pilot flame establishing period and 10 or 15 second main flame establishing period; 5 second early spark termination.; 120 Vac (+10%/-15%), 50/60 Hz supply; 10 W maximum power dissipation; 2000 VA maximum connected load; 15 A type SC fusing.; Post purge of 15 seconds; prepurge determined by the plug-in ST7800A purge timer card; lockout interlocks with preignition interlock.; Five sequence LEDs, five-function Run/Test switch, nonvolatile memory retaining history files and lockout status after power loss.; Rated for -40 deg C to +60 deg C operating ambient, 85% RH noncondensing humidity and 0.5G vibration; weighs approximately 0.7 kg.; UL Component Recognized (File No. MP268), CSA Certified (LR95329-3), FM Approved, Swiss Re acceptable, FCC Part 15 Class B and SIL 3 Capable.
Product categoryBurner control module
Operating voltage120 Vac (+10%/-15%), 50/60 Hz (+/-10%)
Power dissipation10 W maximum
Max connected load2000 VA
Operating temperature-40 deg C to +60 deg C
Main flame establishing period10 s or 15 s
Pilot flame establishing period4 s or 10 s