ModelR7861A1026
Net weight71 g
ApplicationsTypical applications include high-integrity flame supervision in commercial and industrial gas, oil, and combination-fuel burner systems using Honeywell 7800 SERIES burner controls, where dynamic self-checking ultraviolet flame detection is mandated or preferred for safety-critical combustion installations such as power boilers, process heaters, refinery heaters, and large industrial furnaces.
Key featuresDynamic self-check design periodically verifies the connected C7061 self-check ultraviolet flame detector and all amplifier electronic components.; Selectable flame failure response time of 2.0 or 3.0 seconds to match system safety requirements.; Flame signal strength ranges from 0.0 to 5.0 Vdc, with a minimum acceptable signal of 1.25 Vdc for reliable flame confirmation.; Solid-state plug-in module mounts via a keyed printed circuit board edge connector on 7800 SERIES relay modules.; Compatible with C7061 self-check ultraviolet flame detectors for gas, oil, and coal burner applications.; Purple or blue color-coded housing identifies the dynamic self-check ultraviolet amplifier type within the 7800 SERIES family.; UL listed (File No. MP268, Guide MCCZ) and CSA certified (File No. LR95329-3) for North American safety compliance.; Operating ambient temperature range of -40 to 60 degrees Celsius for industrial environments.
Product categoryIndustrial combustion component - Dynamic self-check ultraviolet flame amplifier for 7800 SERIES burner controls
Flame signal range0.0 to 5.0 Vdc
Product dimensionsWidth 91 mm; height 85 mm; depth 23 mm
Operating temperature-40 to 60 degrees Celsius
Minimum acceptable signal1.25 Vdc
Flame failure response time2.0 or 3.0 seconds (selectable)