ModelR7851C1008
MountingPlug-in, keyed edge connector
ApplicationsTypical applications include flame supervision in commercial and industrial gas, oil, and combination-fuel burner systems using Honeywell 7800 SERIES burner controls, where dynamic self-checking flame detection is required for safety-critical combustion installations such as boilers, process heaters, and furnaces.
Key featuresDynamic self-check design periodically tests the connected flame detector and all amplifier electronic components during normal operation.; Selectable flame failure response time of 2.0 or 3.0 seconds to match application safety requirements.; Flame signal strength output ranges from 0.0 to 5.0 Vdc, measurable via test jacks or the 7800 SERIES keyboard display module.; Plug-in module mounts through a keyed printed circuit board edge connector on 7800 SERIES relay modules, ensuring proper orientation.; Compatible with C7961E and C7961F ultraviolet flame detectors for gas, oil, and coal burner applications.; White color-coded housing identifies the dynamic self-check optical amplifier type within the 7800 SERIES product family.; Operating ambient temperature range of -40 to 60 degrees Celsius for demanding industrial environments.
Product categoryIndustrial combustion component - Dynamic self-check optical flame amplifier for 7800 SERIES burner controls
Flame signal range0.0 to 5.0 Vdc
Operating temperature-40 to 60 degrees Celsius
Flame failure response time2.0 or 3.0 seconds (selectable)