ModelR7851B1018
ApplicationsTypical applications include flame signal amplification in 7800 SERIES burner management systems on industrial gas, oil or coal fired burners using C7927 or C7962 optical (ultraviolet/visible light) flame detectors.
Key featuresOptical flame detection covering ultraviolet and visible light; white color-coded label identifies the detection type.; Flame failure response time of 0.8 or 1.0 seconds, depending on amplifier and relay module selection.; Dynamic Ampli-Check circuitry tests all flame amplifier components 12 times per minute; the relay module locks out on amplifier failure.; Flame signal test jacks measure flame signal voltage; 0.0 to 5.0 Vdc reading range; minimum acceptable signal 1.25 Vdc.; Plugs into the 7800 SERIES relay module through a printed circuit board edge connector keyed for proper orientation.; Suitable for gas, oil and coal fired burners.; Operating temperature -40 F to +140 F (-40 C to +60 C); weighs approximately 2.5 oz (71 g).; UL Listed (File No. MP268, Guide No. MCCZ), CSA Certified (File No. LR95329-3), FM Approved (Report No. 1V9A0.AF).
Product categoryFlame signal amplifier
Flame signal range0.0 to 5.0 Vdc
Flame detection typeOptical
Operating temperature-40 to +60 C
Flame failure response time0.8 or 1.0 seconds
Minimum acceptable flame signal1.25 Vdc