ModelR7849A1023
ApplicationsTypical applications include flame supervision in gas and oil burner systems equipped with Honeywell 7800 SERIES burner controls, where standard ultraviolet flame detection without dynamic self-checking is acceptable, such as commercial boilers, heating plants, and industrial process burners using C7027/C7035/C7044 UV detectors.
Key featuresUltraviolet flame detection type, compatible with C7027, C7035, and C7044 Minipeeper ultraviolet flame detectors.; Flame failure response time of 2.0 or 3.0 seconds, selectable to suit the application safety profile.; Flame signal voltage range of 0.0 to 5.0 Vdc, with a minimum acceptable flame signal of 1.25 Vdc for reliable detection.; Solid-state plug-in design mounts via a keyed printed circuit board edge connector on 7800 SERIES relay modules.; Flame signal test jacks allow direct measurement of amplifier flame signal voltage using a high-impedance voltmeter.; Purple color-coded label identifies the ultraviolet non-self-check amplifier within the 7800 SERIES family.; Operating ambient temperature range of -40 to 60 degrees Celsius (-40 to 140 degrees Fahrenheit).
Product categoryFlame signal amplifier
Flame signal range0.0 to 5.0 Vdc
Flame detection typeUltraviolet
Operating temperature-40 to 60 degrees Celsius
Minimum acceptable signal1.25 Vdc
Flame failure response time2.0 or 3.0 seconds