ModelR7847B1031
ApplicationsTypical applications include gas, oil and coal fired industrial burners, boilers and process heating equipment using Honeywell 7800 Series burner management systems that need a 2.0 or 3.0 second flame failure response.
Key featuresR7847B amplifier with dynamic Ampli-Check circuitry that tests the amplifier components twelve times per minute during burner operation and shuts the burner down if the amplifier fails.; Flame failure response time of 2.0 or 3.0 seconds depending on the selected relay module; the Honeywell catalog lists this model as a 2 or 3 second FFRT amplifier.; Compatible with gas rectifying flame rods (C7004, C7005, C7007, C7008, C7009, Q179) and with gas, oil or coal ultraviolet detection using C7012A,C detectors.; Flame signal strength range of 0.0 to 5.0 Vdc; minimum acceptable flame signal 1.25 Vdc; test jacks provided for measurement.; Green color-coded label identifies rectification detection type; plug-in edge connector keyed for proper orientation.; Operating ambient temperature -40 to 140 F (-40 to 60 C) at up to 85 percent relative humidity; weight 2.5 oz (71 g).
Product categoryFlame signal amplifier
Flame signal range0.0 to 5.0 Vdc
Ambient temperature-40 to 140 F (-40 to 60 C)
Flame detection typeRectification
Diagnostic configurationAMPLI-CHECK
Flame detection principleRectification
Flame failure response time2.0 or 3.0 seconds