ModelR7847A1033
ApplicationsTypical applications include flame supervision in commercial and industrial gas burner systems using Honeywell 7800 SERIES controls with rectifying flame rods, such as atmospheric gas burners, power burners, boiler burners, and process heaters where standard flame rectification detection without dynamic self-checking is acceptable and C7000-series flame rods or Q179 pilots are installed.
Key featuresRectification-type flame detection, compatible with flame rods C7004, C7005, C7007, C7008, C7009, Q179 gas pilot, and C7012A/C UV detectors.; Flame failure response time of 2.0 or 3.0 seconds, selectable to match application safety requirements.; Flame signal strength output ranges from 0.0 to 5.0 Vdc, measurable via amplifier test jacks.; Solid-state plug-in design mounts via a keyed edge connector on 7800 SERIES relay modules.; Non-self-check (standard) configuration; does not include dynamic detector or circuit self-test.; Green color-coded label identifies the rectification flame amplifier within the 7800 SERIES family.; Operating ambient temperature -40 to 60 degrees Celsius for industrial environments.; UL listed and CSA certified for North American safety compliance.
Self checkingNone (standard)
Product categoryFlame signal amplifier
Flame signal range0.0 to 5.0 Vdc
Flame detection typeRectification
Operating temperature-40 to 60 degrees Celsius
Diagnostic configurationStandard amplifier
Flame detection principleRectification
Flame failure response time2.0 or 3.0 seconds