ModelR7847A1025
ApplicationsTypical applications include flame supervision in automatically fired gas, oil and combination-fuel single-burner systems built on Honeywell 7800 SERIES or R7140 burner control relay modules.
Key featuresResponds to rectified flame signals from flame rods, rectifying photocells or C7012A/C solid state ultraviolet detectors.; Flame failure response time selectable; the exact options depend on the relay module used (0.8 or 1.0 second, or 2.0 or 3.0 seconds).; Flame signal strength reading range 0.0 to 5.0 Vdc measured through flame signal test jacks; minimum acceptable flame signal 1.25 Vdc.; Plugs into the relay module through a printed circuit board edge connector keyed for proper orientation.; Green color-coded label identifies the rectification flame detection type.; Operating ambient temperature -40 to +60 degrees C, humidity 85% RH continuous noncondensing.
Product categoryIndustrial combustion safety component - rectification flame amplifier for burner management relay modules
Flame signal range0.0 to 5.0 Vdc
Diagnostic configurationStandard amplifier
Flame detection principleRectification
Flame failure response timeselectable, depends on relay module
Minimum acceptable flame signal1.25 Vdc