ModelQ624A1014
Net weight1400 g
Firing rate60 sparks/s
ApplicationsUsed on commercial and industrial gas burners for interrupted ignition of gas pilots, including boilers and process heating equipment, where a solid-state spark generator provides reliable light-off in the same mounting space as conventional ignition transformers.
Key featuresOperates on 120 Vac, 50/60 Hz with a primary VA rating of 66 VA.; Output voltage 10,000 volts, with a firing-cycle peak voltage of 15,000 volts open circuit and 22,000 volts peak-to-peak nonsinusoidal.; Firing rate 60 sparks per second; energy discharge 200 millijoules per spark; discharge time 0.3 milliseconds per spark.; Power dissipation approximately 12 watts per second; maximum high-voltage lead length 15 ft (4.6 m).; Impervious to humidity up to 95 percent relative humidity.; Recommended for interrupted ignition applications only.; Mounts in the same space used by conventional ignition transformers and weighs 3 lb (1.4 kg).; Prevents detection of the ignition spark when properly applied with C7027, C7035 or C7044 Minipeeper ultraviolet flame detectors.
Output voltage10,000 V
Product categoryIndustrial combustion component - Solid-state spark generator (ignition transformer) for gas burners
Maximum spark gap1/4 in (6 mm)
Operating voltage120 Vac, 50/60 Hz
Primary va rating66 VA
Product dimensionsWidth 108 mm; height 172 mm; depth 76 mm
Firing cycle peak voltage15,000 V (open circuit)