ModelMMI811.1
MountingPlug-in, 12-pin S98 wiring base
Fuse rating10A rapid / 6A slow maximum
ApplicationsTypical applications include automatic safety control of 2-stage forced draught gas and combination oil/gas burners in commercial and industrial boilers, water heaters, heating plants, and process heating systems, where EN 298 compliant burner management with ionization or infrared flame detection and two-stage fuel control is required for burners of any nominal thermal load.
Key featuresDesigned for 2-stage forced draught and combination oil/gas burners with intermittent operation, approved per EN 298.; 220/240 VAC (-15 to +10 percent) at 50 Hz (50-60 Hz compatible); frequency variations cause proportional timing deviations.; Power consumption approximately 10 VA; maximum fuse rating 10A rapid or 6A slow.; Flame detection via ionization electrode or infrared flicker detector (IRD 1020).; Integrated air pressure monitoring, flame lift-off protection, and low-voltage protection.; Programmable timing sequences including pre-purge, ignition, safety time, and second-stage delay by model variant.; Plug-in construction with 12-pin S98 wiring base for convenient installation and replacement.; Transparent flame-retardant plastic housing, IP40 dust protection, operating temperature -20 to +60 degrees Celsius.; External reset device support for manual lockout reset after safety shutdown.
Flame detectionIonization electrode or IR flicker detector (IRD 1020)
Product categoryIndustrial combustion component - Gas burner automatic safety control (Satronic MMI 811.1) for 2-stage forced draught and combi oil/gas burners
Protection classIP40
Operating voltage220/240 VAC (-15 to +10%), 50 Hz (50-60 Hz)
Power consumptionapproximately 10 VA
Operating temperature-20 to +60 degrees Celsius