Skip to content
Industrial combustion components support@rifuze.com

Honeywell

Honeywell L404A1396 Line Voltage Pressure Controller

Product photo unavailable

Model
L404A1396

Technical Specifications

ModelL404A1396
Reset TypeAutomatic
Switch TypeSPST, breaks on pressure rise
ApplicationsOperating control or high-limit pressure cutoff on steam boiler installations, mounted above the boiler waterline using a siphon loop to maintain a protective water seal.; Pressure supervision and automatic limit regulation in industrial fluid and piping systems carrying compressed air, non-combustible gases, ammonia, or oxygen.
Key featuresRegulates operating pressures across a range of 10 to 150 psi with an adjustable subtractive differential between 8 and 16 psi and a maximum surge pressure of 225 psi.; Employs a stainless steel pressure diaphragm compatible with steam, air, non-combustible gases, ammonia, oxygen, and distilled water.; Incorporates a dustproof sealed mercury switch with internal screw terminals and a side knockout for 1/2-inch electrical conduit.; Provides internal 1/4-18 NPT female pipe connections on the base hexagonal fitting as well as dual knockouts for surface mounting.; Equipped with top-mounted adjustment screws, dual-scale markings in psi and kg/cm2, a clear plastic cover, and an internal leveling pendulum.; Rated for electrical contact loads of 8.0 full-load amps at 120 Vac and 5.1 full-load amps at 240 Vac.
Product categoryLine Voltage Pressure Controller
Differential TypeAdjustable, subtractive
Differential Range8–16 psi
Maximum Surge Pressure225 psi
Operating Pressure Range10–150 psi

Get a quote

Honeywell · L404A1396

The Honeywell L404A1396 Pressuretrol controller provides line voltage operating control or automatic limit protection for pressurized systems. The device monitors system pressure via a stainless steel diaphragm sensing element and actuates an internal single-pole single-throw mercury switch that breaks the electrical circuit on pressure rise when pressure reaches the selected setpoint. Once pressure drops by the subtractive differential value below the setpoint, the circuit automatically remakes.

Supply information

The quotation confirms the actual items, accessories and commercial terms for your order.

Item condition
To be confirmed in your quotation
Packaging
To be confirmed in your quotation
Included accessories
To be confirmed in your quotation
Stock confirmation
To be confirmed in your quotation
Dispatch / lead time
To be confirmed in your quotation
Price conditions
To be confirmed in your quotation
Warranty provider
To be confirmed in your quotation

More components in this catalog