ModelEC7895A1010
Humidity85% RH maximum, noncondensing
Net weight900 g
Pilot typeIntermittent
ApplicationsTypical applications include on/off primary safety control for commercial and industrial gas, oil, and combination-fuel burners with intermittent pilot ignition in boilers, water heaters, process heaters, and furnaces, where a 220/240 VAC microprocessor-based 7800 SERIES control with integrated safety logic and self-diagnostics is required for single-burner installations of any capacity.
Key featuresMicroprocessor-based integrated burner control for automatically fired gas, oil, or combination-fuel single burners.; 220/240 VAC (+10/-15 percent) power supply at 50/60 Hz for international installations.; On/off primary control with intermittent pilot operation; pilot flame establishing period of 4 or 10 seconds.; Maximum total connected load of 2000 VA with 15A fast-acting fuse; power dissipation 10W maximum.; Plug-in module requiring a Q7800 subbase, compatible flame amplifier, and pre-purge timer card.; Internal hardware status monitoring verifies purge card parity, jumper integrity, and internal circuitry.; Closed-loop logic test confirms integrity of all safety-critical loads and terminal circuits.; Operating ambient temperature -40 to 60 degrees Celsius, humidity up to 85 percent RH noncondensing.; Compatible with remote monitoring via Honeywell Thermal IQ Connected Plant solution.
Product categoryBurner control module
Operating voltage220/240 VAC (+10/-15%), 50/60 Hz
Power dissipation10 W maximum
Max connected load2000 VA
Operating temperature-40 to 60 degrees Celsius
Pilot flame establishing period4 or 10 seconds