ModelDWR625
ApplicationsTypical applications include maximum or minimum pressure monitoring of steam systems according to TRBS, hot water systems to DIN EN 12828, and fuel gas or liquid fuel supply lines, for example as a pressure monitor or limiter with external interlock in combustion plants and boiler rooms.
Key featuresSetting range 0.5 to 6 bar; mean switching differential approximately 0.25 bar; maximum permissible working pressure 25 bar.; Bursting pressure above 100 bar for all DWR types, verified by TUV test; device tested with 2 million switching cycles as special construction.; Stainless steel pressure bellows sensor (material no. 1.4571) with welded, seal-free construction; die-cast aluminium switch housing GD AlSi 12 resistant to seawater corrosion.; Pressure connection G 1/2 external thread to DIN 16288 and G 1/4 internal thread to ISO 228 Part 1, gas applications only up to 4 bar.; Protection class IP 54; ambient temperature at the switching device -20 to +70 deg C; medium temperature -25 to +70 deg C.; Switching point adjustable with the setting spindle; single-pole changeover contact; suitable for maximum and minimum pressure monitoring.; Designed to meet SIL 2 according to IEC 61508-2; TUV and DVGW component tests exist.
Setting range0.5 to 6 bar
Product categoryBuilding and industrial automation component - mechanical pressure monitor (pressure switch) for steam, hot water, fuel gas and liquid fuel systems
Protection classIP 54
Bursting pressure>100 bar
Medium temperature-25 to +70 deg C
Ambient temperature-20 to +70 deg C
Pressure connectionG 1/2 external thread, G 1/4 internal thread
Max working pressure25 bar
Switching differentialapprox. 0.25 bar (mean)