ModelDWR6-301
ApplicationsTypical applications include maximum or minimum pressure monitoring of steam systems according to TRBS, hot water systems to DIN EN 12828, and fuel gas or liquid fuel supply lines, for example as a pressure monitor or limiter with external interlock in combustion plants and boiler rooms.
Key featuresSetting range 0.5 to 6 bar; switching differential fixed, mean value approximately 0.2 bar; maximum permissible working pressure 16 bar.; Terminal connection version (housing 300) with M16 x 1.5 cable entry; protection class IP 65 in vertical position.; Stainless steel pressure bellows (1.4571) with welded, seal-free construction; die-cast aluminium housing GD AlSi 12.; Calibrated for rising pressure; switching point adjustable via setting spindle; single-pole changeover microswitch.; Pressure connection external thread G 1/2 to DIN 16288 and internal thread G 1/4 to ISO 228 Part 1, gas only up to 4 bar.; Ambient temperature -20 to +70 deg C; medium temperature -25 to +70 deg C; bursting pressure above 100 bar verified by TUV.; Tested with 2 million switching cycles; designed to meet SIL 2 according to IEC 61508-2.
Setting range0.5 to 6 bar
Product categoryBuilding and industrial automation component - mechanical pressure monitor (pressure switch) for steam, hot water, fuel gas and liquid fuel systems
Protection classIP 65 (vertical)
Pressure connectionG 1/2 external thread, G 1/4 internal thread
Max working pressure16 bar
Electrical connectionTerminal connection, M16 x 1.5 cable entry
Switching differentialfixed, approx. 0.2 bar (mean)