Skip to content
Industrial combustion components support@rifuze.com

Honeywell

Honeywell C7061A1079 Dynamic self-check ultraviolet flame detector

Honeywell C7061A1079 · view 1
Manufacturer
Honeywell
Model
C7061A1079

Get a quote

Honeywell · C7061A1079

The Honeywell C7061A1079 is a solid-state electronic ultraviolet flame sensor engineered to detect ultraviolet radiation generated during the combustion of carbon-containing fuels, including natural gas, liquefied petroleum gases, and oil. Designed for continuous industrial burner supervision, the detector incorporates an internal mechanical shutter mechanism that performs dynamic self-checking to verify sensor operation without interrupting burner firing.

Technical Specifications

LensCollimating lens 124204
ModelC7061A1079
ShutterYes
ApplicationsContinuous flame monitoring on industrial boilers, process furnaces, and thermal oxidizers firing natural gas, LP gas, or liquid fuels.; Supervision in complex flame sighting geometries where two sensors wired in parallel prevent false flame-out trips during unsteady combustion.; Integration with Honeywell burner management systems, such as EC/RM7800 series controllers with dynamic self-check amplifiers, SLATE systems, or R4348 flame switches.
Key featuresIntegrates an oscillating mechanical shutter supporting dynamic self-check routines for continuous-duty flame monitoring.; Features a dual-voltage shutter coil compatible with both 120 Vac and 230 Vac operating systems.; Equipped with an integrated focusing lens to optimize ultraviolet radiation collection from the flame target.; Houses an ultraviolet power sensing tube requiring no external power supply for radiation detection.; Provides a standard three-quarter-inch NPT mechanical connection for straightforward mounting on industrial sight pipes.; Enclosed in a robust IP66-rated housing rated for ambient operating temperatures between -40 and 80 degrees Celsius.; Permits parallel electrical wiring of two detectors to reduce nuisance burner shutdowns in difficult sighting configurations.; Supplied with zero-meter integral cabling for direct field wiring into local junction boxes or conduits.
Product statusDiscontinued
Mounting thread3/4 in NPT
Product categoryDynamic self-check ultraviolet flame detector
Operating voltage120 or 230 V AC, 50/60 Hz
Ambient operating temperature−40 to +175 °F

Flame detector: purchasing checks

Review these fields for the complete ordering code. Unconfirmed fields can be included with your enquiry.

Detection principle
To be confirmed for the exact model
Compatible controller / amplifier
To be confirmed for the exact model
Operating mode
To be confirmed for the exact model
Operating voltage
120 or 230 V AC, 50/60 Hz
Connection / mounting
To be confirmed for the exact model
Self-checking
To be confirmed for the exact model

Supply information

The quotation confirms the actual items, accessories and commercial terms for your order.

Item condition
To be confirmed in your quotation
Packaging
To be confirmed in your quotation
Included accessories
To be confirmed in your quotation
Stock confirmation
To be confirmed in your quotation
Dispatch / lead time
To be confirmed in your quotation
Price conditions
To be confirmed in your quotation
Warranty provider
To be confirmed in your quotation