ModelC7061A1038
ShutterYes
Mounting3/4 inch NPT flange for sight pipe
ConnectorBrad Harrison 41310
Net weight1200 g
ApplicationsTypical applications include flame supervision on gas- and oil-fired commercial and industrial burners, boilers, process heaters, and other combustion systems managed by Honeywell 7800 SERIES burner controls, where periodic self-checking of the flame detector is required by the control logic.
Key featuresDynamic self-checking: an oscillating shutter interrupts ultraviolet radiation reaching the sensing tube about 12 times per minute when used with the R7861 amplifier and 7800 SERIES control, converting sensor failures into a safety shutdown.; Rated 120 Vac, 50/60 Hz; mounting flange with 3/4 inch NPT internal threads attaches the detector to a sight pipe.; Wired via a Brad Harrison 41310 connector instead of leadwires, with a threaded conduit fitting for rapid electrical installation.; Violet cast-aluminum housing with separate mounting flange (integral protective heat block) and faceplate; meets NEMA 4 enclosure requirements.; Field-replaceable ultraviolet sensing tube and quartz viewing window rated for 20 psi (138 kPa).; Ambient operating temperature range from -40°F to +175°F (-40°C to +79°C) with the low-temperature sensing tube.; This model has been discontinued by Honeywell and is superseded by the C7061A1046.
Mounting thread3/4 in NPT
Product categoryUltraviolet flame detector
Operating voltage120 VAC
Product dimensionsWidth 133 mm; height 130 mm; depth 183 mm
Ambient temperature range-40°F to +175°F (-40°C to +79°C)
Ambient operating temperature−40 to +175 °F
Viewing window pressure rating20 psi (138 kPa)