ModelC7061A1020
Wiringterminal block
ShutterYes
Mounting3/4 inch NPT flange for sight pipe
Net weight3300 g
ApplicationsTypical applications include flame supervision on gas- and oil-fired commercial and industrial burners, boilers, process heaters, and other combustion systems managed by Honeywell 7800 SERIES burner controls, where periodic self-checking of the flame detector is required by the control logic.
Key featuresDynamic self-checking: an oscillating shutter interrupts ultraviolet radiation reaching the sensing tube about 12 times per minute when used with the R7861A amplifier and 7800 SERIES control, converting sensor failures into a safety shutdown.; Dual-voltage variant rated 115/230 Vac, 50/60 Hz, with a terminal block and a threaded leadwire opening in the faceplate for conduit connection.; Mounting flange with 3/4 inch NPT internal threads attaches the detector to a sight pipe; detector can be mounted horizontally, vertically, or at any angle.; Violet cast-aluminum housing with separate mounting flange (integral protective heat block) and faceplate; meets NEMA 4 and IP66 enclosure requirements.; Field-replaceable ultraviolet sensing tube and quartz viewing window rated for 20 psi (138 kPa).; Ambient operating temperature range from -40°F to +175°F (-40°C to +79°C) with the low-temperature sensing tube.; Two detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Mounting thread3/4 in NPT
Product categoryIndustrial combustion safety component - dynamic self-check ultraviolet (UV) flame detector (Purple Peeper series)
Operating voltage115/230 Vac, 50/60 Hz
Ambient temperature range-40°F to +175°F (-40°C to +79°C)
Ambient operating temperature−40 to +175 °F
Viewing window pressure rating20 psi (138 kPa)