ModelC7035A1056
Mountingintegral collar, 1-11-1/2 NPSM internal threads for 1 in sight pipe
Lead length12 ft
ApplicationsUsed for flame supervision on commercial and industrial gas, oil, and combination burners in boilers, furnaces, and process heaters, typically mounted on a one-inch sight pipe that views the flame through the combustion chamber wall.
Key featuresMinipeeper ultraviolet flame detector with end viewing; it detects ultraviolet radiation only and can sight most common gas and oil flames at up to six feet under optimum conditions.; Integral collar with 1-11-1/2 NPSM internal threads mounts directly on a one-inch sight pipe; the rear of the detector has 1/2-14 NPSM internal threads for conduit connection.; Maximum pressure rating of 5 psi (34.5 kPa); housing meets NEMA enclosure standards types 4 and 4X and is UL rated rain tight.; Supplied with 12 ft (3.66 m) color-coded, silicon rubber insulated 18 AWG NEC Class 1 leadwires; ambient rating is -40°F to +250°F (-40°C to +121°C).; Designed for use with RA890G devices or R7249A/B, R7290A, R7749B, and R7849A/B flame signal amplifiers and the appropriate Honeywell controls.; Compact size of 38 mm diameter by 105 mm long, weighing about 0.17 kg (6 oz); sensing tube life is about 40,000 hours of continuous use.; Not rated for continuous operation; the burner should cycle or be periodically checked at least once every 24 hours per industry guidance.
UV sensor tube129464N
Leadwire length12 ft (3.66 m)
Mounting thread1 in NPT
Product categoryUltraviolet flame detector
Max pressure rating5 psi (34.5 kPa)
Ambient temperature range-40°F to +250°F (-40°C to +121°C)
Ambient operating temperature−40 to +250 °F